| General |
| Degree of protection | IP20 |
| Nominal current | 20 A |
| Switching power | 6 kA |
| Switching curve | C |
| Operating voltage | 230/400 V |
| Number of poles | 1 way |
| Width of device | 1 TE |
| Connection type | Rear busbar |
The circuit breaker
5SL6120-7 from Siemens belongs to the SENTRON series and is designed for safe short-circuit and overload protection in standard applications in residential and commercial buildings. It is a 1-pole device with a rated current of 20 A and a switching capacity of 6 kA. The tripping curve is of type
C, indicating medium sensitivity to overloads and typical for applications with motor loads or consumers with high inrush currents. The device is designed for operating voltages of 230/400 V and is therefore suitable for single-phase and three-phase installations in the low-voltage range.
Applications
The circuit breaker 5SL6120-7 is used in electrical distributions to protect lines and consumers against thermal overloads and short circuits. It is particularly suitable for installations in residential buildings, office buildings, and other commercial buildings where reliable and simple protection functions are required. The tool-free mounting and dismounting simplifies installation and maintenance, especially in modular installation systems.
Functions and Equipment in Detail
The device features a rear-mounted busbar, enabling simple and quick wiring of the supply. The busbar reduces mounting time and improves the clarity of the installation. The switching function is operated via a handle, which visually indicates the state of the switch (on, off, tripped). Tripping occurs automatically when the type C tripping curve is reached or when short-circuit currents exceed 6 kA.
Technology Explained Simply
The tripping curve
C means that the switch trips at a current of approximately 5 to 10 times the rated current (i.e., 100 A to 200 A at a rated current of 20 A) within seconds. For lower overloads (e.g., 1.13 times rated current), the switch trips after a time delay to tolerate short-term current peaks. The switching capacity of
6 kA describes the maximum short-circuit energy that the device can safely interrupt without damage. The operating voltage of
230/400 V covers common low-voltage networks in Germany.
Compatibility and Accessories
The circuit breaker 5SL6120-7 is expandable with various accessories that extend its functionality. These include auxiliary switches such as the 5ST3010 (1 NO + 1 NC) or the 5ST3062 (changeover switch), which can be used for signaling or remote control. Additionally, pin busbars such as the 5ST3740 (3-phase, 10 mm²) or the 5ST3708 (3-phase, 16 mm², fully insulated) are available, enabling safe and structured connections between devices. Spacers such as the 5TG8240 (0.5 TE) support mounting in modular installation systems.
Mounting and Installation
Mounting is tool-free in standard distribution boxes with modular installation systems. The rear busbar enables direct and secure connection to the supply. Installation requires no additional tools, and positioning within the distribution board is defined by the standard TE width (here 1 TE). Wiring is done via the front connection terminals, designed for connection to cables.
Advantages in Operation
The switch offers high reliability and easy handling. Tool-free mounting reduces installation time, and the clear indication of the switch state simplifies maintenance. Compatibility with a wide range of accessories allows flexible adaptation to specific requirements, such as remote monitoring or signaling systems. The protection functions are designed for use in standard installations and meet the requirements for safety and reliability in the low-voltage range.