Siemens 5SL43026, EAN: 4001869439471

Siemens 5SL4302-6 circuit breaker 3-pole 2 A

Installation > Modular devices / equipment installation > Circuit breaker

Siemens 5SL4302-6 circuit breaker 3-pole 2 A

Lieske Part No. 1586091
Mfg Part No 5SL43026
EAN-Code 4001869439471
Manufacturer Siemens
Here only 99,00 EUR
117,81 EUR incl. VAT

Further information for Siemens 5SL4302-6 circuit breaker 3-pole 2 A

General
Degree of protectionB
Nominal current2 A
Switching voltage400 V
Short-circuit withstand capability10 kA
Number of poles3
Device familySENTRON 5SL4
Mounting methodtool-free
Built-in width1 TE
The circuit breaker 5SL4302-6 from Siemens belongs to the SENTRON series and is designed for safe short-circuit and overload protection in standard applications in residential and utility buildings. It is a 3-pole device with a rated current of 2 A and a switching voltage of 400 V. The Type B protection enables the protection of consumers with typical load characteristics, such as those found in lighting systems, heating, or small electrical appliances. The device is designed for a short-circuit current of 10 kA, ensuring high safety in case of sudden overloads.

Applications
The switch is intended for use in indoor electrical distributions, particularly in residential buildings, office buildings, and other utility structures. It protects electrical lines and connected consumers against thermal overload and short circuits. The 3-pole design makes it especially suitable for three-phase power networks, for example in distribution boxes for main or branch circuits.

Functions and Equipment in Detail
The circuit breaker 5SL4302-6 offers tool-free mounting and dismounting, simplifying installation and maintenance in the distribution box. The rear-mounted busbar allows for easy and quick wiring of the supply, reducing mounting time. The switching function is operated via a visible lever, clearly indicating the state (on/off). The Type B design ensures selective tripping during overloads, reducing the likelihood of unnecessary disconnections.

Technology Explained Simply
Type B protection responds to continuous overloads at approximately 1.3 times the rated current (here 2.6 A) within minutes, while immediate tripping occurs during sudden short circuits (at approximately 5 times the rated current). The rated voltage of 400 V covers typical three-phase networks in Germany. The short-circuit withstand rating of 10 kA means the device operates safely even under high current surges in the network without damage. The 3-pole design protects all three phases simultaneously, which is important for safety in three-phase installations.

Compatibility and Accessories
The device is part of the extensive SENTRON family and can be expanded with various accessories. These include auxiliary switches such as the 5ST3062-0MC or 5ST3020, which enable additional signaling functions such as make or break contacts for controls or indicators. Also, handle locks (e.g. 5ST3806) or locking devices (e.g. 5ST3807) can be installed to control access to the device. Pin busbars such as the 5ST3738 or 5ST3740-1 support wiring and provide a safe, shock-protected connection. Compatibility with these accessories allows flexible adaptation to specific requirements in electrical installations.

Mounting and Installation
Mounting is tool-free in standard distribution boxes with a depth of 70 mm. The rear busbar enables a direct and secure connection to the supply. Installation is simple and error-free thanks to clear labeling and mechanical guidance of the device. The mounting width is 1 module (1 TE), enabling compact placement in distributors. Wiring is done via the front terminals, while the rear busbar simplifies the supply connection.

Advantages in Operation
The switch offers high reliability and safety due to its robust construction and precise tripping characteristic. Tool-free mounting reduces installation time and minimizes the risk of mounting errors. Compatibility with accessories extends functionality without impairing the basic function. The clear indication of the switching state simplifies maintenance and inspection of the device. Type B protection ensures a balanced response to overloads, increasing the availability of the electrical system.