| General |
| Phases | 1 |
| Rated power (S6) | 1,6 kVA |
| Short-term power | 7,3 kVA |
| Primary voltage | 400 V |
| Primary voltage deviation | +/-5 % |
| Secondary voltage | 110 V |
| Secondary current | 14,5 A |
| Frequency | 50...60 Hz |
| Switching group | II0 |
| Shielding value | 0 |
| Ambient temperature class | 40 °C |
| Insulation class | B |
| Degree of protection | IP00 |
| Connection type | Screw and flat pin connection |
| Mounting method | Screws |
| Compliance with standards | EN 61558-2-1, -2-2, -2-4 |
| Approval | UL/CSA-recognized |
The Siemens transformer type 4AM6142-5AJ10-0FA0 is a single-phase isolation transformer from the SITAS series, designed for use in industrial automation systems and control applications. It serves as a safety and control transformer, enabling galvanic isolation between primary and secondary sides to ensure electrical safety and immunity to interference. The transformer is rated for a nominal power of 1.6 kVA (S6) and a short-time power of 7.3 kVA, making it suitable for applications with short-term load peaks. The primary voltage is 400 V ±5 %, and the secondary voltage is 110 V, with the secondary side being loadable up to 14.5 A. The operating frequency ranges from 50 to 60 Hz, enabling use in various international power supply systems.
Applications
The transformer is intended for use in industrial control and regulation systems, particularly in installations requiring galvanic isolation between the power supply and load. It is suitable, for example, for powering control devices, relays, contactors, or other electronic components in automation technology. The high short-time power rating also makes it suitable for applications with short-term load peaks, such as motor start-up or actuation of electromechanical switches. The single-phase design is typical for applications in small to medium-sized industrial systems.
Functions and Equipment in Detail
The transformer features winding group II0 and a shielding factor of 0, indicating a standard construction without additional shielding. The insulation class B and ambient temperature class TA 40 °C indicate an operating temperature up to 40 °C, which is sufficient for use in controlled industrial environments. The protection class IP00 means the transformer is not protected against mechanical impacts or moisture and must therefore only be installed in enclosed, dry, and dust-free rooms. Connections are made via screw and flat pin terminals, enabling flexible and secure connections to cables and wiring. Mounting is done using screws, ensuring a secure attachment to a wall or within an enclosure.
Technology Explained Simply
Galvanic isolation between primary and secondary sides is achieved through magnetic coupling of the two windings via the iron core. This eliminates any direct electrical connection between the power supply and the load, increasing safety and preventing disturbances in the network. The nominal power of 1.6 kVA (S6) refers to continuous load capacity, while the short-time power of 7.3 kVA is permitted for short durations (e.g., 10 minutes). The secondary voltage of 110 V is typical for powering control devices and auxiliary circuits. The frequency range of 50 to 60 Hz allows use in various countries with different power grid standards. Insulation class B ensures sufficient thermal load capacity for the insulation materials.
Compatibility and Accessories
The transformer complies with standards EN 61558-2-1, -2-2, and -2-4, which define requirements for safety transformers, isolation transformers, and control transformers. It is also UL/CSA-recognized, indicating approval by the respective North American safety organizations. The design is intended for use in enclosures and industrial control systems, with mounting via screws.
Mounting and Installation
Mounting is done using screws, and the transformer must be installed in a closed, dry, and dust-free room. The protection class IP00 requires that it be protected from mechanical impacts, moisture, and dust. Connections are made via screw and flat pin terminals, enabling secure and reliable connections. Adhering to the specified operating temperature of 40 °C is important to ensure the device’s lifespan and reliability.
Operational Advantages
The transformer offers high reliability through galvanic isolation, minimizing network disturbances and increasing safety. The short-time power of 7.3 kVA enables operation of loads with short-term current peaks without overloading the transformer. Compliance with international standards such as EN 61558 and UL/CSA-recognized facilitates approval and use in various markets. Simple mounting and clear terminal design support quick and error-free installation in industrial systems.