| General |
| Product type | Power-cut-out switch |
| Product series | 3VA6 |
| Degree of protection | ETU860 |
| Protection functions | LSIG |
| Rated current | 600 A |
| Switching capacity | 150 kA |
| Operating voltage | 480 V |
| Number of poles | 4 |
| Overload protection range | 240-600 A |
| Short-circuit protection Isd | 0,6-9 x In |
| Instantaneous protection Ii | 1,5-9 x In |
| N-conductor protection | adjustable (OFF, up to 100%) |
| Earth fault protection Ig | 0,2-1 x In |
| Earth fault protection time tg | 0,05-0,8 s |
| Approval | UL |
| Mounting method | fixed installation, plug-in/insert technology |
| System | SENTRON 3VA |
The power circuit breaker
3VA6460-8KQ41-0AA0 from Siemens is a compact power circuit breaker of the SENTRON 3VA6 series, designed for use in industrial installations with high safety requirements. It features UL certification and is suitable for use in fixed mounting as well as in plug-in and withdrawable technology. The circuit breaker is 4-pole and has a rated current of 600 A, with the switching capacity class L defined at 150 kA at 480 V. It provides effective system protection by safely disconnecting in the event of overload or short circuit. The integrated protection device ETU860 enables precise and adjustable protection functions with parameters LSIG, covering overload protection (L), short-circuit protection (S), instantaneous protection (I), and earth fault protection (G).
Applications
This power circuit breaker is designed for use in industrial electrical installations, particularly in environments where high reliability and protection functions are required. The UL certification allows use in installations that must comply with American safety standards. The 3VA6 series is globally applicable, as it meets both IEC and UL standards. The 4-pole configuration makes it suitable for systems with a neutral conductor, for example in low-voltage networks with 3-phase-plus-neutral systems.
Functions and Equipment in Detail
The circuit breaker offers an adjustable overload protection with a range of 240 A to 600 A (Ir). The short-circuit protection is adjustable via two parameters: the selective short-circuit protection (Isd) ranges from 0.6 to 9 times the rated current (In), and the instantaneous protection (Ii) ranges from 1.5 to 9 times In. The neutral conductor protection is also adjustable and can be deactivated (OFF) or set up to 100 % of the rated current. The earth fault protection (Ig) is adjustable between 0.2 and 1 times In, with a time delay (tg) of 0.05 to 0.8 seconds. These functions enable a differentiated protection configuration that can be adapted to the specific requirements of the respective installation.
Technology Explained Simply
The ETU860 protection device is an electronic protection unit that continuously monitors the electrical parameters of the installation. When the set threshold values are reached, the circuit breaker automatically trips to prevent damage to the installation or hazards to personnel. The adjustability of the protection parameters allows for optimal tuning to the load characteristics of the connected devices. The 4-pole configuration ensures that the neutral conductor is also disconnected in case of overload or short circuit, which is particularly important in installations with asymmetric load distribution. The UL certification ensures compliance with safety requirements in the USA and Canada.
Compatibility and Accessories
The power circuit breaker is part of Siemens' SENTRON system and can be extended with modular accessories that are uniformly available for all sizes and series of 3VA compact power circuit breakers. Suitable accessories include, for example, the Powermanager V4.X license download for up to 10 devices, enabling central monitoring and control of the circuit breakers. The modular design simplifies installation and maintenance and allows flexible adaptation to different requirements.
Mounting and Installation
The circuit breaker is designed for mounting in fixed installations as well as in plug-in and withdrawable technology. Installation is carried out in standard switchboards or enclosures, with the size and required dimensions matching the respective requirements. The uniform modular design of the 3VA series facilitates integration into existing systems and reduces space requirements in the enclosure.
Advantages in Operation
The combination of UL certification and IEC standard enables worldwide use of the device. The adjustable protection functions offer high flexibility in adapting to different load profiles. The modular expandability and compatibility with other sizes in the 3VA series reduce inventory costs and simplify maintenance. The high switching capacity class of 150 kA at 480 V ensures safe disconnection even at high short-circuit currents.