| General |
| Degree of protection | LSIG |
| Rated current | 40 A |
| Overload protection range | 16-40 A |
| Short-circuit protection Isd | 0,6-10 x In |
| Short-circuit protection Ii | 1,5-12 x In |
| Earth fault protection Ig | 0,375-1 x In |
| Earth fault protection time | 0,05-0,8 s |
| Switching capacity | 65 kA |
| Voltage | 480 V |
| System protection type | ETU860 |
| Number of poles | 3 |
| Approval | UL |
| Product series | 3VA6 |
| Frame size | 150 |
| N-conductor protection | optional with external power supply |
| Earth fault current monitoring | up to 160% In |
The power circuit breaker
3VA6140-6KQ31-2AA0 from Siemens is a compact power circuit breaker of the SENTRON 3VA6 series, designed for use in industrial plants with high safety requirements. It features UL certification and is designed for use in Frame 150. The circuit breaker provides comprehensive plant protection through integrated protection functions and is available in 3-pole configuration. It is suitable for mounting in fixed installation as well as in plug-in and insert technology, enabling flexible integration into existing control systems. The 3VA6 series is characterised by modular expandability and compact design, thereby minimising space requirements.
Applications
The circuit breaker is designed for use in industrial electrical installations, particularly in plants requiring a high switching capacity and reliable protection against overload and short circuit. The UL certification enables use in installations that must comply with American safety standards. The 3VA6 series is globally applicable, as it meets both IEC and UL standards. This makes it especially suitable for international projects where compliance with various standards is required.
Functions and Equipment in Detail
The circuit breaker features an integrated plant protection type ETU860 with LSIG functions (L = overload protection, S = selectivity, I = short-circuit protection, G = earth fault protection). The rated current is 40 A, with the overload protection range (Ir) adjustable from 16 A to 40 A, covering 100 % of the rated load. Short-circuit protection is implemented via the settings Isd (0.6 to 10 x In) and Ii (1.5 to 12 x In). For earth fault protection, a range of 0.375 to 1 x In is available, with a time delay of 0.05 to 0.8 seconds. Neutral conductor protection is optionally achievable with an external current transformer, enabling earth fault current monitoring up to 160 % of the rated current. The protection functions enable safe disconnection in the event of a fault, thereby minimising damage to the plant and risks to personnel.
Technology Explained Simply
The circuit breaker operates with a switching capacity class H, enabling a switching capacity of 65 kA at 480 V. This means it is capable of safely interrupting a short-circuit current of up to 65,000 amperes at a voltage of 480 volts. The integrated electronics of the ETU860 module allow precise adjustment of the protection functions, ensuring optimal protection of the plant. The modular design enables combination with various accessories required for specific requirements such as remote control, status indication, or communication. The 3VA6 series is part of a unified system standardised for all sizes and series of compact power circuit breakers 3VA.
Compatibility and Accessories
The circuit breaker is compatible with modular accessories of the SENTRON 3VA series. Suitable accessories include, for example, the Powermanager V4.X license download, which supports up to 10 devices. This accessory enables remote monitoring and control of the circuit breakers, making plant maintenance and diagnostics more efficient. The modular expandability ensures that additional functions such as status indication, remote operation, or communication modules can be easily retrofitted.
Mounting and Installation
The power circuit breaker is designed for mounting in fixed installation as well as in plug-in and insert technology. The modular design and uniform interface for accessories simplify installation and maintenance. Mounting is carried out in standard control panels, with the frame size Frame 150 to be taken into account. The circuit breakers are designed to be installed without additional tools or special mounting aids, reducing installation time.
Advantages in Operation
The circuit breaker provides reliable protection against overload and short circuit, thereby increasing the operational safety of the plant. The modular expandability allows adaptation to specific requirements without impairing basic functionality. The UL certification extends the application range in international projects. The integrated protection functions reduce the likelihood of failures and damage, thereby extending the operational life of the plant. The unified system architecture of the SENTRON 3VA series simplifies maintenance and interchangeability of components.