| General |
| Switching capacity | 25 kA |
| Operating voltage | 415 V |
| Poles | 3 |
| Rated continuous current | 40 A |
| Overload protection | 28...40 A |
| Short-circuit protection | 5...10 x In |
| Switching capacity class | N |
| System protection | TM240, ATAM |
| Terminal connection | terminal connection |
| Construction type | Compact power circuit breaker |
| IEC frame size | 160 |
The Siemens circuit breaker type 3VA1140-3EF36-0AA0 belongs to the SENTRON 3VA1 series and is designed as a compact circuit breaker for use in industrial and commercial electrical installations. It provides effective system protection by safely disconnecting in the event of overload or short circuit. The breaker is available in 3-pole configuration and corresponds to IEC frame size 160, making it suitable for fixed mounting as well as plug-in and insert technology. The modular design allows flexible adaptation to different operational requirements.
Applications
The circuit breaker is used in electrical installations where reliable protection against overload and short circuit is required. It is suitable for use in industrial machines, drive technology, lighting systems, and other electrical systems where a high protection standard is required. The switching capacity class N with a switching capacity of Icu=25kA at 415V makes it suitable for installations with high short-circuit currents. The rating for 3 poles and a rated continuous current of 40A enables use in medium to high power requirements.
Functions and Equipment in Detail
The breaker features an integrated overload protection with an adjustable rated current Ir in the range of 28A to 40A. This protection responds to sustained overloads and disconnects the circuit to prevent damage to systems and wiring. Additionally, short-circuit protection is integrated, operating within a setting range of 5 to 10 times the rated current (Ii=5...10 x In). This ensures rapid disconnection in case of sudden short circuits. The protection functions are part of the system protection TM240 and ATAM, ensuring reliable and precise disconnection.
Technology Explained Simply
The breaker operates on the principle of thermal-magnetic protection. The thermal component responds to continuous overloads by heat generation, while the magnetic component reacts immediately to sudden high currents, such as during short circuits. The combination of both protection principles ensures comprehensive protection for the electrical installation. The terminal connection type allows for simple and secure connection of conductors. The modular design of the breaker permits integration of various accessories, such as connection extenders, front rotary drives, or terminal covers, which may be required depending on the application.
Compatibility and Accessories
The circuit breaker is compatible with a wide range of accessory components that extend its functionality. These include, for example, connection extenders (e.g. 3VA9153-0QC00), front rotary drives (e.g. 3VA9157-0EK21), round conductor terminal blocks (e.g. 3VA9113-0JB11), and terminal covers (e.g. 3VA9111-0WD30). These accessories are uniformly designed for all sizes of the 3VA series and can be added as needed. The use of additional components such as DC insulation plates (e.g. 3VA9113-0SG10) or locking devices (e.g. 3VA9088-0LB10) allows individual adaptation to specific operational requirements.
Mounting and Installation
The breaker is designed for fixed mounting as well as plug-in and insert technology, enabling flexible installation in various enclosures and distributions. Mounting is done using standard mounting elements, with the exact procedure following the respective manufacturer’s installation instructions. The modular design simplifies installation and maintenance, as individual components such as terminals or drives can be easily replaced or added.
Advantages in Operation
The use of the Siemens 3VA1140-3EF36-0AA0 provides high reliability and safety in electrical installations. The integrated protection functions ensure comprehensive protection against overload and short circuit. The modular design allows flexible adaptation to different requirements without needing to replace the base breaker. Compatibility with a wide range of accessories increases application versatility and simplifies maintenance and expansion of the installation. The low height and compact design save space in the enclosure, which is particularly advantageous in confined installations.