| General |
| Manufacturer | Siemens |
| Product type | Monitoring relay |
| Function | Earth fault monitoring |
| Technology | Digital |
| Series | SIRIUS |
| Supply voltage | 24 to 240 V |
| Voltage type | AC/DC |
| Frequency range | 50 to 60 Hz |
| Adjustable range of warning threshold | 0.03 to 40 A |
| Adjustable range of trip value | 0.03 to 40 A |
| Start and trip delay | 0.1 to 20 s |
| Switch-off hysteresis | up to 50 % |
| Warning hysteresis | 5 % |
| Indication | actual value or fault type |
| Self-monitoring | permanent |
| Clamps | Removable |
| Connection system | Screw connection |
| Changeover contact | 2 |
| Fault memory | Switchable |
| Accessory compatibility | Residual current transformer 3UL23 series |
| Accessories | plombable cover, adapter, identification plates |
| Status | end-of-life product |
| Successor | 3UG5625-1CW30 |
The Siemens monitoring relay type 3UG4625-1CW30 is a digital residual current monitoring relay from the SIRIUS series, designed for continuous monitoring of electrical installations for fault currents. It is used to detect leakage currents caused by dust accumulation, moisture, porous cables, or capacitive effects. The device is intended for use in industrial and commercial installations where reliable fault current detection is required to prevent fire hazards and ensure electrical safety. The operating voltage covers a wide voltage range of AC/DC 24 to 240 V, enabling worldwide application. Frequency ranges of 50 Hz and 60 Hz are supported, allowing the relay to be used in various power grids.
Applications
This relay is primarily designed for residual current monitoring in electrical installations, especially in environments with an increased risk of leakage currents, such as production facilities, machine building, building technology, or installations with high humidity or dust content. It can be used in both indoor and outdoor installations, provided the environmental conditions comply with the technical specifications. The application typically occurs in enclosures, where the device is installed to monitor lines, motors, or other electrical components.
Functions and Equipment in Detail
The device features digital parameterization via a menu system. The adjustable ranges for warning threshold and trip value are between 0.03 A and 40 A, with both values being independently adjustable. The start-up and trip delay can be set between 0.1 and 20 seconds, allowing flexible adaptation to different installation conditions. The trip hysteresis is up to 50 %, while the warning hysteresis is fixed at 5 %. These settings ensure precise and reliable response to fault currents, minimizing false trips. The relay continuously displays the actual value or the type of fault, enabling quick diagnosis. Measurement accuracy is high, and the device performs continuous self-monitoring to ensure functionality.
Technology Explained Simply
This transformer measures the difference between incoming and outgoing current, thereby detecting fault currents. The relay itself processes these measured values digitally and compares them with the set limit values. When the warning threshold is exceeded, a signal is triggered; when the trip value is exceeded, the affected line is switched off. The display shows the current actual value or the type of fault, enabling quick fault localization. The removable terminals allow device replacement without rewiring, simplifying maintenance. The screw connection technology ensures a secure and durable connection.
Compatibility and Accessories
The relay is compatible with various residual current transformers from the 3UL23 series, available in different lengths (e.g. 35 mm, 55 mm, 80 mm, 105 mm, 140 mm, 210 mm) and with an adjustable range of 30 mA to 40 A. Combining it with a suitable transformer is required to ensure functionality. Additionally, accessories such as sealable covers (e.g. 3RP1902), adapters for screw mounting (e.g. 3RP1903), or device identification plates can be used. These components are uniformly available for all SIRIUS relays and serve for securing, labeling, or mechanical mounting.
Mounting and Installation
Mounting is done in standard enclosures. The device has a width of 22.5 mm, making it space-saving. Installation requires connection to a residual current transformer from the 3UL23 series, which can be mounted either inside or outside the enclosure. The screw connection technology enables a secure and durable connection. Parameterization is done via the integrated menu system, with the actual value display aiding in precise setting of limit values. Commissioning is quick, as no special programming is required.
Advantages in Operation
The relay offers high flexibility through separate setting of warning and trip values, as well as adjustable delay time. The continuous display of the actual value or fault type enables quick diagnosis. Self-monitoring ensures device reliability. Removable terminals simplify replacement without rewiring. Using a residual current transformer from the 3UL23 series allows flexible positioning, simplifying installation in complex systems. The wide voltage supply and international certifications enable use in various countries and power grids.
The device is marked as a discontinued product. The preferred successor is the digital residual current monitoring relay 3UG5625-1CW30, which is also combined with a residual current transformer from the 3UL23 series. The functions and technical specifications of the successor are comparable, although possibly with extended features.
Residual current monitoring,
digital relay,
SIRIUS series,
residual current transformer,
screw connection,
wide voltage supply