| General |
| Construction size | S00 |
| Degree of protection | CLASS 10 |
| A-trip unit adjustment range | 4,5-6,3 A |
| N-trigger | 82 A |
| Connection system | Spring clamp connection |
| Switching capacity | Standard |
| Product series | SIRIUS 3RV2 |
| Application range | Motor protection |
| Approvals | IEC, UL/CSA |
| Explosion-proof | ATEX, IEC Ex |
The Siemens power switch type 3RV2011-1GA20 belongs to size S00 and is specifically designed for motor protection. It features a CLASS 10 A-trip unit with an adjustable range of 4.5 to 6.3 A and an N-trip unit with 82 A. The switch is equipped with spring-cage terminals, enabling fast, maintenance-free, and vibration-resistant connections. It provides safe disconnection in case of short-circuit, protects consumers and systems from overload, and allows for safe isolation of the system from the power supply. Its compact design and low heat dissipation make it particularly suitable for use in consumer branches, including systems with IE3- and IE4-motors.
Applications
The power switch 3RV2011-1GA20 is intended for various applications in industrial environments. It is used for motor protection, also serving as an overload relay function. Additionally, it is suitable for system protection, short-circuit protection of starter combinations, transformer protection, and as a main or emergency stop switch. The devices are also designed for use in IT networks. Worldwide approvals according to standards such as IEC and UL/CSA, as well as suitability for hazardous areas (ATEX or IEC Ex), extend the range of applications in international and special use cases.
Functions and Equipment in Detail
The switch offers standard switching capacity and is part of the SIRIUS 3RV2 series, which replaces the previous 3RV1 series. Size S00 enables compact mounting, especially in enclosures with limited space. The spring-cage terminal technology ensures a secure and reliable connection without additional tools. The integrated motor protection function protects the connected motor from overload and short-circuit, with the CLASS 10 A-trip unit handling the thermal overload protection. The N-trip unit ensures rapid disconnection in case of short-circuit events.
Technology Explained Simply
The CLASS 10 A-trip unit refers to the thermal trip characteristic, which triggers after approximately 10 seconds at 10 times the rated current during overload. The adjustable range of 4.5 to 6.3 A allows adaptation to various motor ratings. The N-trip unit with 82 A ensures rapid disconnection in case of short-circuit, protecting the electrical system from damage. The spring-cage terminal technology reduces installation time and increases reliability, as no additional screw connections are required. The low heat dissipation of the device minimizes thermal load in the enclosure.
Compatibility and Accessories
The power switch is compatible with a comprehensive accessory system designed to extend functionality. Compatible components include auxiliary switches such as the 3RV2901-2A or 3RV2901-2C, which are side-pluggable, and auxiliary trip units such as the 3RV2902-2DB0 for voltage trip units in the AC 20–24 V range. Other accessories include door coupling rotary drives such as the 3RV2926-3C for difficult conditions or the 3RV2926-1C for emergency stop functions. Device adapters such as the 8US1251-5DS11 enable mounting in the 60 mm busbar system. Accessories are uniformly available for all sizes of the SIRIUS 3RV2 series.
Mounting and Installation
Mounting is done via the spring-cage terminal system, enabling fast and secure connections. Size S00 is designed for use in enclosures with limited space. Using the associated SIRIUS 3RV29 power supply system significantly reduces main circuit wiring. The devices are designed for use with various power supply options, increasing flexibility during installation. Mounting requires no additional tools, making installation efficient and maintenance-free.
Advantages in Operation
The power switch 3RV2011-1GA20 offers high reliability through integrated motor protection and rapid disconnection in case of short-circuit. Low heat dissipation reduces thermal load in the enclosure and extends the lifespan of components. The spring-cage terminal technology ensures vibration-resistant connections, which is particularly beneficial in moving or vibrating environments. Worldwide approvals and suitability for hazardous areas expand the application range in international and special applications. Compatibility with a comprehensive accessory system allows flexible adaptation to different requirements.