| General |
| Construction size | S00 |
| Degree of protection | Motor protection |
| A-trigger | CLASS 10 |
| A-trip range | 3,5-5 A |
| N-trigger | 65 A |
| Connection type | Screw connection |
| Switching capacity | Standard switching capacity |
| Accessory compatibility | SIRIUS 3RV29, auxiliary switch, auxiliary trip unit |
The Siemens power switch type 3RV2011-1FA10 belongs to size S00 and is specifically designed for motor protection. It features a CLASS 10 A-trip unit with an adjustable range of 3.5 to 5 amperes, as well as an N-trip unit with a rated value of 65 amperes. The switch is equipped with screw terminals and offers standard switching capacity. It ensures safe disconnection in the event of a short circuit and protects consumers and installations against overload. Additionally, it enables safe isolation of the installation from the network. The compact design and weather-resistant construction make it particularly suitable for use in consumer branch circuits, especially for IE3- and IE4-motors. The low heat dissipation of the device reduces thermal stress in the enclosure.
Applications
The power switch is intended for various applications in industrial environments. It can be used as a motor protection switch, also fulfilling the function of an overload relay. Other applications include installation protection, short-circuit protection for starter combinations, transformer protection, and use as a main or emergency stop switch. The switch is also suitable for use in IT networks. Worldwide approvals according to standards such as IEC and UL/CSA, as well as suitability for hazardous areas (ATEX or IEC Ex), significantly expand the range of applications.
Functions and Equipment in Detail
The switch features a CLASS 10 A-trip unit responsible for overload protection. The N-trip unit with 65 A provides short-circuit protection. The screw terminal connection ensures a secure and vibration-resistant connection. The devices are optionally available with an integrated auxiliary switch, which facilitates integration into control systems. The comprehensive accessory program includes various auxiliary switches, auxiliary trip units, and signaling switches, all uniformly available for all sizes of the SIRIUS 3RV2 series.
Technology Explained Simply
The CLASS 10 A-trip unit responds to an overload within a maximum of 10 seconds, with the exact tripping time depending on the load level. The N-trip unit disconnects quickly in the event of a short circuit to prevent damage to the installation. The screw terminal construction enables a stable and maintenance-free connection of the conductors. The low heat dissipation of the device is particularly advantageous in densely populated enclosures, as it reduces thermal stress and increases the service life of components.
Compatibility and Accessories
The power switch is part of the SIRIUS system building kit and can be combined with various accessories. These include auxiliary switches in different configurations, such as horizontal or side-pluggable, as well as undervoltage trip units for various voltage ranges. The use of the SIRIUS 3RV29 power supply system enables reduction of main circuit wiring. The accessories are uniformly available for all sizes of the 3RV2 series, increasing interchangeability and flexibility.
Mounting and Installation
The switch is mounted in standard control panels or enclosures. The screw terminal construction requires no special tools and allows for quick and secure connection. Mounting typically takes place in a vertical or horizontal control panel area. The installation dimensions correspond to size S00, suitable for compact installations. Wiring is carried out according to the electrical diagrams and the requirements of the respective standards.
Advantages in Operation
The use of the power switch 3RV2011-1FA10 provides high operational safety through the combination of overload and short-circuit protection. The low heat dissipation and weather-resistant design increase reliability in demanding environments. Worldwide approvals enable use in international projects. Integration into the SIRIUS system allows for flexible and modular expansion of the installation. The use of auxiliary switches and additional trip units extends functionality and supports control and monitoring of the installation.
The power switches of the 3RV2 series replace the proven 3RV1 series and offer a modern, efficient, and up-to-date solution for industrial use. The system is designed for easy handling and high reliability.