| General |
| Construction size | S00 |
| Rated current range | 2,8-4,0 A |
| A-trigger | CLASS 10 |
| N-trigger | 52 A |
| Connection type | Screw connection |
| Switching capacity | Standard switching capacity |
| Approvals | IEC, UL/CSA |
| Application range | Explosion-hazard areas (ATEX/IEC Ex) |
| System | SIRIUS 3RV1 |
The Siemens motor protection circuit breaker type 3RV1011-1EA10 belongs to size S00 of the SIRIUS series and is specifically designed for motor protection in industrial installations. It provides safe disconnection in the event of short-circuit and protects consumers and systems from overload. Additionally, it enables safe isolation of the installation from the power supply. The circuit breaker is optimized for use in consumer branches, particularly for motors with efficiency class IE3 or IE4, and features low heat generation. It has a screw connection and is suitable for use in IT networks as well as in hazardous areas (ATEX or IEC Ex). Worldwide approvals according to IEC and UL/CSA are standard.
Applications
This motor protection circuit breaker is intended for use in industrial installations, particularly in consumer branches. It is suitable for drives with rated currents between 2.8 and 4.0 A. Size S00 allows for compact mounting in enclosures and is certified for applications in hazardous areas. Use in IT networks is also possible, with switching functions meeting electrical safety requirements.
Functions and Equipment in Detail
The circuit breaker features a CLASS 10 A-trip unit, providing protection against overload and short-circuit. The N-trip unit is rated for 52 A and ensures safe disconnection at high current levels. The switching functions are optimized for use in consumer branches, with low heat generation enabling thermally stable operation. The circuit breaker is equipped with a screw connection, ensuring a secure and reliable connection. The integrated switching function enables safe isolation of the installation from the power supply.
Technology Explained Simply
The motor protection circuit breaker operates on the principle of thermal and magnetic tripping. The thermal trip unit responds to sustained overloads by monitoring heat development in the circuit and tripping the switch when the specified current range (2.8–4.0 A) is exceeded. The magnetic trip unit ensures immediate disconnection during sudden current surges, such as those occurring during short-circuits. The CLASS 10 designation means the switch trips within 10 seconds at an overload of 10 times the rated current. The 52 A rated current for the N-trip unit is designed for short-circuit protection. The screw connection variant enables a mechanically stable and electrically reliable connection.
Compatibility and Accessories
The circuit breaker is part of the SIRIUS system building kit and can be combined with various accessories. Compatible components include auxiliary switches in different configurations, such as horizontal or side-mounted, as well as undervoltage release units for size S00/S0. Auxiliary switches enable control of auxiliary functions, such as signaling or remote control. Using the SIRIUS 3RV29 power feed system significantly reduces main circuit wiring. Accessories are uniformly available for all sizes in the SIRIUS system.
Mounting and Installation
The motor protection circuit breaker is mounted in enclosures and designed for installation in consumer branches. Mounting is done using the designated mounting elements, with the screw connection variant ensuring a secure mechanical connection. Installation must follow the requirements of relevant standards and approvals, particularly for use in hazardous areas. Wiring is done via the screw terminals, with electrical connections made according to technical specifications.
Advantages in Operation
The circuit breaker offers high reliability through the combination of thermal and magnetic tripping. Low heat generation ensures thermally stable operation, extending the device’s service life. Worldwide approvals enable use in various markets. Compatibility with the SIRIUS system building kit and various accessories provides flexibility in adapting to specific requirements. Switching functions are suitable for use in IT networks, ensuring electrical safety. Size S00 allows for compact mounting, reducing space requirements in enclosures.