General
Construction size
S00
Degree of protection
Motor protection
A-trigger
CLASS 10
A-trip unit adjustment range
1,4-2,0 A
N-trigger
26 A
Connection type
Screw connection
Switching capacity
Standard switching capacity
Approvals
IEC, UL/CSA
Explosion-proof
ATEX, IEC Ex
Use in IT networks
The Siemens motor protection circuit breaker type 3RV1011-1BA10 belongs to size S00 of the SIRIUS series and is specifically designed for motor protection. It provides safe disconnection in the event of a short circuit and protects consumers and systems from overload. Additionally, it enables safe isolation of the system from the power supply. The compact design and weather-resistant construction make it particularly suitable for use in consumer branch circuits, especially for motors of efficiency class IE3 or IE4. The low heat dissipation of the device reduces thermal stress in the enclosure and supports reliable operation under industrial conditions.
Applications
This circuit breaker is designed for use in industrial systems where reliable protection for electric motors is required. It is particularly suitable for applications where safe disconnection and protective functions are necessary in the event of a fault. Global certification according to standards such as IEC as well as UL/CSA enables use in various markets. Additionally, variants for use in hazardous areas (ATEX or IEC Ex) are available, extending application possibilities to special industrial environments. The devices are also suitable for use in IT networks.
Functions and Equipment in Detail
The motor protection circuit breaker features a CLASS 10 A-trip unit with an adjustable range of 1.4 to 2.0 A and an N-trip unit with a value of 26 A. These trip units ensure precise response to overload and short circuit conditions. The circuit breaker is equipped with screw terminals, ensuring a secure and stable connection in the main current circuit. The standard version offers standard switching capacity, sufficient for typical industrial applications. The devices are available in various variants, including main and emergency stop circuit breakers.
Technology Explained Simply
The circuit breaker operates on the principle of motor protection, interrupting the current flow automatically in the event of a fault (e.g., overload or short circuit). The CLASS 10 A-trip unit responds to thermal overload, with the tripping time depending on the load level. The N-trip unit ensures rapid disconnection in the event of a short circuit. The screw terminal version enables a mechanically stable connection suitable for industrial requirements. The low heat dissipation of the device reduces thermal stress in the enclosure and contributes to long service life.
Compatibility and Accessories
The device is part of the SIRIUS system building kit, allowing it to be combined with a wide range of accessories. Compatible components include auxiliary switches in various configurations, such as side-mounted (e.g. 3RV2901-1B, 3RV2901-1C, 3RV2901-1J) or horizontal (e.g. 3RV2901-1D, 3RV2901-1G, 3RV2901-1E), as well as under-voltage release units (e.g. 3RV2902-1AB0, 3RV2902-1AB4, 3RV2902-1AS0, 3RV2902-1AV0) and voltage release units (e.g. 3RV2902-1DF0, 3RV2902-1DP0). Additionally, connection modules (e.g. 3RA1911-1AA00) and 3-phase busbars (e.g. 3RV1915-1BB, 3RV1915-1AB) are available, simplifying wiring in the main current circuit. Accessories are uniformly designed for all sizes of the SIRIUS system.
Mounting and Installation
Mounting is carried out in standard enclosures, with size S00 enabling compact placement. The screw terminal requires mechanically secure fastening of the conductors. The use of accessories such as auxiliary switches or release units is achieved through mechanical or electrical connections, depending on the type. Integration into existing control systems is simple and efficient due to the standardization of the SIRIUS system. Wiring in the main current circuit can be simplified by using the SIRIUS 3RV29 power feed system.
Operational Advantages
The circuit breaker provides reliable protection for motors and systems, with low heat dissipation enhancing operational safety. Standardization of the SIRIUS system enables easy expansion and maintenance. Global certification facilitates use in international projects. The availability of various accessories allows flexible adaptation to specific requirements without impairing basic functionality. The combination of motor protection, isolation function, and compact design makes the device a versatile solution in industrial electrical engineering.