| General |
| Adjustment range | 7,0-10 A |
| Protection class | CLASS 10 |
| Construction size | S00 |
| Type of electrical connection of main circuit | screw |
| Connection type auxiliary circuit | screw |
| Reset function | Manual-automatic RESET |
| Degree of protection | Thermal |
| Application | Motor protection |
| Approvals | IEC, UL/CSA |
| Explosion-proof | ATEX, IEC Ex |
The Siemens overload relay type 3RU2116-1JB0 belongs to the SIRIUS product range and is designed as a thermal overload relay for motor protection. It is designed for size S00 and serves for current-dependent protection of consumers with normal start-up against excessive heating caused by overload or phase failure. The device is intended for mounting on contactors and features an adjustment range of 7.0 to 10 amperes. The protection class is CLASS 10, which means a specific time delay for tripping under overload conditions. The main and auxiliary current circuits are equipped with screw terminals, ensuring a secure and vibration-resistant connection. A manual-automatic RESET allows for manual or automatic reset after tripping.
Applications
This overload relay is used in industrial applications where electric motors must be protected against thermal overload. It is particularly suitable for installations requiring high operational reliability, such as in manufacturing, packaging, or food processing industries. The worldwide certification according to IEC and UL/CSA, as well as suitability for hazardous areas (ATEX or IEC Ex), extends its application range in demanding environments.
Functions and Equipment in Detail
The device operates thermally, with tripping triggered by the heating of a heating element that reacts proportionally to the load current. The adjustment ranges allow adaptation to various motor powers. The screw terminals ensure a robust connection that remains stable even under vibration conditions. The manual-automatic RESET offers flexibility for restarting after a tripping event.
Technology Explained Simply
The thermal tripping function is based on heating a bimetal strip, which triggers a mechanical movement when the set current value is exceeded, thereby interrupting the current circuit. The CLASS 10 classification means that the relay trips within 2 to 20 minutes at an overload of 1.5 times the rated current. This time range is suitable for motors with normal start-up requiring a short starting phase. The screw terminals are designed for secure mounting and prevent loosening under operating conditions.
Compatibility and Accessories
The relay is designed for mounting on contactors of size S00. Suitable accessories include, for example, individual mounting carriers (3RU2916-3AA01), scale covers (3RV2908-0P), and other overload relays for different adjustment ranges, such as model 3RU2116-1JC0 (7.0–10 A) or 3RU2116-1JB0 (4–6 A). The accessories are compatible with all sizes from S00 to S3, enabling flexible system expansion.
Mounting and Installation
Mounting is done directly on the contactor, using the screw terminals for the main and auxiliary current circuits. Installation does not require special tools, as the connections are mechanically secured. Positioning is typically in the main current circuit of the motor to ensure operational safety.
Advantages in Operation
The relay provides reliable protection with minimal maintenance effort. The screw terminals ensure a permanent connection, and the manual-automatic RESET function allows flexible resetting. The worldwide certification and suitability for hazardous areas increase operational safety in demanding environments. Integration into the SIRIUS system building kit ensures high compatibility with other components of the product range.