Further information for Siemens 3NA3824-6 NH fuse 80 A gL/gG
General
Construction size
NH00
Nominal current
80 A
Fuse type
gL/gG
Operating voltage AC
690 V
Operating voltage DC
250 V
Handle bottles
Live voltage-carrying
Front indicator
The Siemens NH fuse insert type 3NA3824-6 belongs to the SENTRON series and is designed for use in electrical installations requiring selective line and system protection. It is manufactured in size NH00 and serves as a protective component in switchgear, where safe disconnection is necessary in case of overload or short circuit. The fuse is equipped with a front indicator, which visually displays the operating status, and features voltage-carrying handle bottles that allow safe handling even under voltage. The fuse is rated for operating voltages up to 690 V AC and 250 V DC.
Applications
The fuse insert 3NA3824-6 is intended for use in industrial and commercial electrical installations, particularly in switchgear that requires high safety standards for the protection of personnel, equipment, and systems. It is used in SENTRON series switchgear devices available in various sizes and rated currents. Size NH00 is suitable for compact installations where space-saving and high protection functions are required. The fuse is designed for use in systems with rated currents up to 80 A and provides reliable protection in electrical networks with voltages up to 690 V AC and 250 V DC.
Functions and Equipment in Detail
The fuse is designed as a gG type, meaning it is suitable for general line protection in electrical installations. The rated current is 80 A, with the fuse safely disconnecting in case of overload or short circuit. The integrated front indicator allows visual inspection of the operating status – it indicates whether the fuse is intact or has tripped. The voltage-carrying handle bottles allow safe insertion and removal of the fuse even under voltage, simplifying maintenance and servicing. The fuse is part of a comprehensive NH fuse system available in various sizes and rated currents.
Technology Explained Simply
The fuse 3NA3824-6 operates on the principle of thermal and electromagnetic disconnection. In case of overload, the fuse link is heated by the heat and melts, interrupting the circuit. In case of short circuit, the high current generates a magnetic field that also quickly melts the fuse link. The combination of thermal and magnetic disconnection enables selective protection, where only the faulty circuit is disconnected while the rest of the system continues to operate. The voltage-carrying handle bottles are designed to ensure electrical insulation during insertion or removal of the fuse.
Compatibility and Accessories
The fuse insert 3NA3824-6 is compatible with NH fuse bases of size 00, particularly with models such as 3NH8030, 3NH6030, 3NH2032, 3NH2030, 3NH1030, and 3NH1032. These bases are available in various designs (ceramic, plastic) and pole configurations (1-pole, 3-pole). Additionally, signal indicators such as 3NX1024 or 3NX1021 can be used to monitor the fuse status. The fuse can also be combined with electrical fuse monitoring devices such as 3KF9010-1AA00 to enable automatic monitoring of the protection status.
Mounting and Installation
Mounting is carried out in suitable NH fuse bases of size 00. The voltage-carrying handle bottles allow insertion and removal of the fuse even under voltage, with electrical insulation ensured by the design of the handle bottles. Installation is done by simply inserting the fuse into the base, where the fuse can be visually checked via the front indicator. The fuse is designed for use in switchgear installations complying with standards for electrical switchgear.
Advantages in Operation
The fuse 3NA3824-6 provides reliable protection in electrical installations through its selective disconnection function. The front indicator enables quick visual inspection of the operating status, simplifying maintenance and servicing. The voltage-carrying handle bottles increase safety during handling, as the fuse can be replaced even under voltage. The use in combination with monitoring systems such as 3KF9010-1AA00 or signal indicators allows an integrated monitoring solution that optimizes system operation.