Further information for Siemens 3NA3236 NH Fuse 160A gL/gG
General
Construction size
2 NH2
Nominal current
160 A
Marking
gG
Nominal voltage AC
500 V
Nominal voltage DC
440 V
Handle bottles
Live voltage-carrying
Front indicator
The Siemens NH fuse insert type 3NA3236 belongs to the SENTRON series and is designed for selective line and system protection. It is used in size 2 (NH2) and provides reliable protection against overload and short circuit in electrical installations. The fuse is equipped with a front indicator, which visually displays the operating status, and features live-handling handles that enable safe handling. SENTRON series fuse inserts are designed for use in industrial and commercial installations where high operational safety and reliability are required.
Applications
The fuse insert 3NA3236 is intended for use in electrical distributions and switchgear, particularly in installations with a rated voltage up to 500 V AC and 440 V DC. It is suitable for protecting lines, motors, transformers, and other electrical devices where selective protection is required to limit the impact of a fault to a minimum. Size 2 enables integration into standard switchgear and distribution boxes designed for this dimension.
Functions and Equipment in Detail
The fuse insert 3NA3236 is equipped with a front indicator that visually displays the fuse status (intact or blown). This facilitates maintenance and inspection, as the operating status can be identified without additional measuring instruments. The live-handling handles ensure that the fuse can be safely replaced even under voltage, as the handles carry the voltage and thus maintain the electrical connection. The fuse is rated for a nominal current of 160 A and complies with the gG marking, which is used for general protection applications in industry and commerce.
Technology Explained Simply
The fuse operates on the principle of thermal and electromagnetic disconnection. In case of overload, the fuse element heats up and melts, interrupting the circuit. In case of a short circuit, the fuse reacts via electromagnetic forces, enabling rapid disconnection. The rated voltage AC 500 V and DC 440 V define the maximum voltages at which the fuse can be safely operated. The gG marking means that the fuse is suitable for general protection of lines and systems, including protection functions for short circuit and overload. Size 2 (NH2) is a standard size used in many distributors and switchgear.
Compatibility and Accessories
The fuse insert 3NA3236 is compatible with other SENTRON products and can be used in combination with various accessories. These include, for example, signal indicator subassemblies such as the 3NX1021, which enable additional signaling, or electrical fuse monitoring devices such as the 3KF9010-1AA00, which allow remote monitoring of the fuse status. Other compatible fuse inserts in size 2 include, for example, types 3NA3230 (100 A), 3NA3244 (250 A), or 3NA3250 (300 A), which can be selected according to the required nominal current.
Mounting and Installation
Mounting is carried out in standard switchgear and distribution boxes designed for size 2. The live-handling handles allow safe insertion and removal, even under voltage, while maintaining the electrical connection during replacement. The fuse is inserted into the corresponding fuse holder and secured by a mechanical locking mechanism. Installation is carried out in accordance with applicable regulations and standards, particularly VDE 0660 and DIN EN 60947-2.
Advantages in Operation
The use of the fuse insert 3NA3236 provides high operational safety through selective protection. The visual indication of the front indicator reduces maintenance time, as the fuse status can be quickly checked. The live-handling handles increase safety during maintenance work, as the power supply does not need to be interrupted during replacement. The gG marking ensures universal applicability in various industrial and commercial environments.