| Complementary |
| Max power consumption in W | 1 mW |
| Number of channels | 16 |
| Modulation Technique | O-QPSK |
| Bandwidth | 5 MHz |
| Antenna gain | 0 dBi |
| Embedding depth | 42 mm |
| CAD overall height | 41.5 mm |
| CAD overall width | 30 mm |
| CAD overall depth | 43 mm |
| Net weight | 0.025 kg |
| Operating travel | 4.3 mm (total travel) |
| Operating force | 10 N C/O changing electrical state |
| Mechanical robustness | Free fall resistance 1000 mm conforming to IEC 60068-2-32 |
| Standards | CSA C22.2 No 14; IEC 60947-1; IEC 60947-5-1; UL 508 |
| Radio agreement | ANATEL; ARIB T66; FCC; ICASA; RSS |
| Communication port protocol | Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4 |
| Maximum sensing distance | 100 m in free field; 25 m transmitter in a plastic box type XAL D and receiver in a metal enclosure; 300 m transmitter in box type XAL D, receiver in metal enclosure and use relay-antenna |
| Acquisition time | 2 ms |
| Response time | < 2 ms |
| Fixing mode | Fixing nut beneath head: 2…2.4 N.m |
| Electrical composition code | PW1 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -40…70 °C |
| Relative humidity | 95 % at -40…70 °C without condensation |
| IP degree of protection | IP30 (back face) conforming to IEC 60529 |
| IK degree of protection | IK03 conforming to IEC 50102 |
| Mechanical durability | 1000000 cycles |
| Shock resistance | 25 gn (duration = 6 ms) for 6000 shocks conforming to IEC 60068-2-27; 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |
| Vibration resistance | 5 gn (f= 11…500 Hz) conforming to IEC 60068-2-6; +/- 10 mm (f= 2…11 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 8 kV (in free air (in insulating parts)) conforming to IEC 61000-4-2; Electrostatic discharge immunity test - test level: 4 kV (on contact (on metal parts)) conforming to IEC 61000-4-2; Susceptibility to electromagnetic fields - test level: 20 V/m (80...3000 MHz) conforming to IEC 61000-4-3; Susceptibility to electromagnetic fields - test level: 6 V/m (3000...6000 MHz, distance = 20 m) conforming to IEC 61000-4-3 |
| Product certifications | CSA; GOST; CCC; C-Tick; UL; BT 2006/95/EC |
| Directives | 1999/5/EC - R&TTE directive; 2004/108/EC - electromagnetic compatibility |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | Harmony XB5 |
| Product or component type | Wireless and batteryless transmitter |
| Device short name | XB5R |
| Bezel material | Plastic |
| Mounting diameter | 22 mm |
| Transmission frequency | 2405 MHz |
| emission class | 5M00G7W |
| Antenna type | Omnidirectional |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.2 cm |
| Package 1 Width | 4.5 cm |
| Package 1 Length | 5.3 cm |
| Package 1 Weight | 18 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 75 |
| Package 2 Height | 15 cm |
| Package 2 Width | 15 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 1.533 kg |
Radio buttons without battery, DM 22 mm Harmony XB5 plastic and XB4 metal. Transmitter for radio buttons without battery, individual components. XB5 transmitter for radio buttons without battery. Mounting adapter ZB5AZ009 (plastic) or ZB4BZ009 (metal) must be ordered separately. Only the front elements ZB4 RZA0 and ZB5 RZA0 are mechanically compatible. Plate must be ordered separately. The plate is installed by Schneider Electric, dismantling is not possible (risk of damage).