| Complementary |
| Power consumption in W | 2 W 48 V DC |
| Power consumption in VA | 6.5 VA 240 V AC 50/60 Hz |
| Input protection type | Internal, electronic |
| safety outputs | 4 NO redundant; 2 NC single |
| safety inputs | 0 extension bus 24 V DC 5 mA |
| Maximum line resistance | 60 Ohm |
| Input compatibility | Normally closed circuit conforming to ISO 14119; XC limit switch conforming to ISO 14119; Mechanical contact conforming to ISO 14119; Normally closed circuit conforming to ISO 13850; Antivalent pair conforming to ISO 14119; OSSD pair conforming to IEC 61496-1-2; 3-wire proximity sensors PNP |
| [Ie] rated operational current | 5 A AC-1 for normally open relay contact; 3 A AC-15 for normally open relay contact; 5 A DC-1 for normally open relay contact; 3 A DC-13 for normally open relay contact |
| [Ith] conventional free air thermal current | 8 A |
| Associated fuse rating | 10 A gG for NO relay output circuit conforming to IEC 60947-1; 4 A gG for NC relay output circuit conforming to IEC 60947-1 |
| Minimum output current | 10 mA for relay output |
| Minimum output voltage | 12 V for relay output |
| Maximum response time on input open | 20 ms |
| [Ui] rated insulation voltage | 250 V (pollution degree 2) conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 4 kV overvoltage category II conforming to IEC 60947-1 |
| Local signalling | LED (green) for power ON; LED (red) for error; LED (yellow) for safety output status |
| Mounting support | 35 mm symmetrical DIN rail |
| Depth | 120 mm |
| Height | 100 mm |
| Width | 22.5 mm |
| Net weight | 0.200 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60947-5-1; IEC 61508-1 functional safety standard; IEC 61508-2 functional safety standard; IEC 61508-3 functional safety standard; IEC 61508-4 functional safety standard; IEC 61508-5 functional safety standard; IEC 61508-6 functional safety standard; IEC 61508-7 functional safety standard; ISO 13849-1 functional safety standard; IEC 62061 functional safety standard |
| Product certifications | TÜV; cULus |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP54 (mounting area) conforming to IEC 60529 |
| Ambient air temperature for storage | -25…85 °C |
| Relative humidity | 5…95 % non-condensing |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Safety Automation |
| Product or component type | Safety module |
| Safety module name | XPSUEP |
| Safety module application | For extending number of safety contacts |
| Function of module | Safety output extension |
| Safety level | Can reach PL e/category 4 for normally open relay contact conforming to ISO 13849-1; Can reach SILCL 3 for normally open relay contact conforming to IEC 62061; Can reach SIL 3 for normally open relay contact conforming to IEC 61508; Can reach PL c/category 1 for normally closed relay contact conforming to ISO 13849-1; Can reach SILCL 1 for normally closed relay contact conforming to IEC 62061; Can reach SIL 1 for normally closed relay contact conforming to IEC 61508 |
| Safety reliability data | MTTFd > 30 years conforming to ISO 13849-1; Dcavg >= 99 % conforming to ISO 13849-1; PFHd = 1.61E-09 conforming to ISO 13849-1; HFT = 1 conforming to IEC 62061; PFHd = 1.61E-09 conforming to IEC 62061; SFF > 99% conforming to IEC 62061; HFT = 1 conforming to IEC 61508-1; PFHd = 1.61E-09 conforming to IEC 61508-1; SFF > 99% conforming to IEC 61508-1; Type = B conforming to IEC 61508-1 |
| Electrical circuit type | Addition to Preventa XPSU base module |
| Connections - terminals | Removable spring terminal block, 0.2...2.5 mm² solid or flexible; Removable spring terminal block, 0.25...2.5 mm² flexible with ferrule single conductor; Removable spring terminal block, 0.2...1.5 mm² solid or flexible twin conductor; Removable spring terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel; Removable spring terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel |
| [Us] rated supply voltage | 48...240 V AC/DC - 10...10 % |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.800 cm |
| Package 1 Width | 14.000 cm |
| Package 1 Length | 15.800 cm |
| Package 1 Weight | 303.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 2.584 kg |
The Harmony XPS Universal safety relays are ideal for use in a variety of safety applications thanks to their selectable safety function and start option using rotary switches on the front. This reduces the number of variants of the devices you need, and the diagnostic function allows states to be easily transferred to a PLC, so that in the event of a fault, downtime is reduced by clear error information. The side connector for connecting to the XPSU safety relay enables direct operation without separate wiring of the control. This relay extension has 4 safe relay normally open contacts and 2 normally closed contacts as outputs. The supply voltage is 48-240 VAC/DC and the connections are made via removable spring-loaded terminals. Installation is done by snapping onto a top-hat rail or screwing onto mounting plates. A uniquely numbered locking band is included to protect the settings under the transparent cover. A wide range of approvals enable international use. Thanks to the Green Premium environmental label, you can receive detailed information on material content, environmental impact and circular economy that supports your sustainability goals.