| Complementary |
| Maximum power dissipation in W | 3 W |
| Integrated connection type | Not connected to backplane expansion bus |
| Switching voltage | 10 V DC |
| Associated fuse rating | 3.5 A, slow-blow |
| Safety level | Can reach category 4 conforming to ISO 13849-1; Can reach PL = e conforming to ISO 13849-1; Can reach SIL 3 conforming to IEC 61508; SILCL 3 conforming to IEC 62061 |
| Quality labels | CE |
| Output type | Relay, 2 NO + 1 NC circuit(s), volt-free |
| Quantity per set | 1 |
| Switching time | 12 ms |
| Maximum switching voltage | 400 V AC; 250 V DC |
| minimum switching current | 20 mA |
| Maximum switching current | 6 A |
| Number of terminal blocks | 4 |
| Local signalling | 1 LED green with PWR marking for power ON; 1 LED green with RUN marking for RUN (status); 1 LED red with E IN marking for internal error; 1 LED red with E EX marking for external error; 2 LEDs orange with ADDR marking for node address; 1 LED green/red with RELAY K1 marking for relay contact |
| Connections - terminals | 2 captive screw clamp terminals, removable terminal block; 1 captive screw clamp terminals, removable terminal block |
| Mounting support | Omega 35 mm DIN rail conforming to EN 50022 |
| Width | 22.5 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
| Net weight | 0.25 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 62061; ISO 13849-1; IEC 61508; IEC 61800-5-1 |
| Product certifications | TÜV; cULus; RCM |
| IP degree of protection | IP20 |
| Ambient air temperature for operation | -10…55 °C |
| Ambient air temperature for storage | -20…85 °C |
| Relative humidity | 10…95 % |
| Pollution degree | 2 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 61800-5-1 |
| Safety reliability data | B10d = 300000 utilisation category AC-15 230 V |
| Insulation | 250 V AC between power supply and housing conforming to IEC 61800-5-1 |
| Overvoltage category | II |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2; Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2; Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3; Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 |
| Vibration resistance | +/-0.35 mm (f= 10…55 Hz) conforming to IEC 61496-1 |
| Shock resistance | 10 gn for 16 ms (1000 shocks on each axis) conforming to IEC 61496-1 |
| Electrical durability | 20000000 cycles |
| Mechanical durability | 20000000 cycles |
| service life | 20 year(s) |
| Logistical informations |
| Country of origin | IT |
| Main |
| Range of product | Preventa Safety automation |
| Product or component type | Safe relay output module |
| Device short name | XPSMCM |
| Electrical connection | Screw terminal |
| [Us] rated supply voltage | 24 V - 20...20 % DC |
| Number of outputs | 2 relay |
| Function of module | Monitoring safety actuators for relay output |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.4 cm |
| Package 1 Width | 15.8 cm |
| Package 1 Length | 12.2 cm |
| Package 1 Weight | 236.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 26 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 6.615 kg |
With the Modicon modular safety controller XPSMCM, safety applications can be easily configured and the system can be flexibly expanded with modules according to the application. This expansion module provides 1 safe relay group output. The relay group consists of 2 relays normally open and 1 relay normally closed. The module serves as a relay extension and is controlled by 2 OSSD outputs in a safety-related manner. A feedback loop (EDM) is available. This module does not come with a backplane bus connector as it is not required. The module has removable screw terminals. This expansion module can be used with all CPU versions. Thanks to the Green Premium eco-label, you can receive detailed information on material content, environmental impact and circular economy that supports your sustainability goals.