| Additional features |
| Power consumption in W | 3 W |
| Power loss in W | 3 W |
| Integrated connection type | Rear panel bus extension |
| Number of terminal blocks | 6 |
| Connections - terminals | 2 screw terminals, non-loosening, removable terminal block |
| Load type | resistive load |
| Channel groups | 8 single channel |
| Safety level | Complies with ISO 13849-1; Can achieve PL = c complies with ISO 13849-1; Can achieve SIL 1 complies with IEC 61508; SILCL 1 complies with IEC 62061 |
| Conformity marking | CE |
| Discrete input voltage | 24 V DC |
| Discrete output voltage | 24 V DC |
| Discrete output current | 100 mA |
| Output load | 60 Ohm |
| Local signalling | 1 LED green with PWR marking for power ON; 1 LED green with RUN (operation) marking for operation (status); 1 LED red with E IN marking for internal error; 1 LED red with E EX marking for external error; 2 LEDs orange with ADDR marking for node address; 8 LEDs green/red with OUT marking for output status |
| Mounting bracket | Omega 35 mm DIN rail corresponds to EN 50022 |
| Depth | 22,5 mm |
| Height | 99 mm |
| Width | 114,5 mm |
| Product weight | 0,25 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Preventa Safety Technology |
| Product or component type | safe output expansion module |
| Device short name | XPSMCM |
| Electrical connection | Screwed terminal |
| [UH,nom] Rated operating voltage | 24 V -20 - +20 % DC |
| Output type | 8 configurable for diagnostic connection |
| Discrete input type | Insulated |
| Discrete output type | DC |
| Module function | Monitoring of safety actuators for discrete output |
| Mounting |
| Standards | IEC 61800-5-1; ISO 13849-1; IEC 61508; IEC 62061 |
| Product certifications | TÜV; RCM; cULus |
| Degree of protection (IP) | IP20 (housing) |
| Operating ambient temperature | -10…55 °C |
| Ambient temperature during storage | -20…85 °C |
| Relative humidity | 10…95 % |
| Pollution degree | 2 |
| [Uimp] Rated impulse voltage withstand | 4 kV corresponds to IEC 61800-5-1 |
| Safety and reliability data | DC > 60 %; MTTFd = 985 years high; PFHd = 4.44E-9 1/h |
| Insulation | 250 V AC between power supply and housing corresponds to IEC 61800-5-1 |
| Over voltage category | II |
| Electromagnetic compatibility | Electromagnetic compatibility test for electrostatic discharge - test level: 6 kV (contact) corresponds to IEC 61000-4-2; Electromagnetic compatibility test for electrostatic discharge - test level: 20 kV (air) corresponds to IEC 61000-4-2; Susceptibility to electromagnetic fields - test level: 10 V/m (80 - 1.000 MHz) corresponds to IEC 61000-4-3; Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 - 2 GHz) corresponds to IEC 61000-4-3 |
| Vibration resistance | ± 0.35 mm (f= 10…55 Hz) complies with IEC 61496-1 |
| Shock resistance | 10 Gn (duration = 16 ms) for 1,000 shocks on each axis, equivalent to IEC 61496-1 |
| Lifespan | 20 years |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 16,0 cm |
| VPE 1 width | 12,5 cm |
| VPE 1 length | 4,3 cm |
| Packaging weight (Lbs) | 219,0 g |
| VPE 2 type | S01 |
| VPE 2 quantity | 6 |
| VPE 2 height | 15,0 cm |
| VPE 2 width | 15,0 cm |
| VPE 2 length | 40,0 cm |
| VPE 2 weight | 1,577 kg |