Further information for Schneider Electric XAPS11221N control enclosure arrow right latching
Complementary
AC control voltage 50 HZ
120…600 V
Cable entry
1 knock-out for cable entry, clamping capacity: 17 mm; 1 tapped entry for cable gland, clamping capacity: 12 mm
AC control voltage 60 HZ
120…600 V
Net weight
0.83 kg
DC control voltage
125…600 V
Connections - terminals
Screw clamp terminals, = 1 x 0.22 mm² without cable end conforming to IEC 60947-1
Number of command positions
1
Tightening torque
0.8…1.2 N.m conforming to IEC 60947-1
Shape of screw head
Cross compatible with Philips no 1 screwdriver; Cross compatible with pozidriv No 1 screwdriver; Slotted compatible with flat Ø 4 mm screwdriver; Slotted compatible with flat Ø 5.5 mm screwdriver
Contacts material
Silver alloy (Ag/Ni)
Maximum resistance across terminals
25 MOhm
Short-circuit protection
10 A cartridge fuse type gG conforming to IEC 60947-5-1
Number of indicator lights
0
[Ith] conventional free air thermal current
10 A conforming to IEC 60947-5-1
[Ui] rated insulation voltage
600 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
[Ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1; 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1; 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1; 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
Compatibility code
XAPS
Number of push buttons
0
Number of selector switches
0
Number of key switches
1
Number of mushroom-shaped push-buttons
0
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
1
Number of contacts as change-over contact
0
Housing material
Metal
Housing colour
Grey
colour of cover
Grey
Emergency power off
Contractual warranty
Warranty (in months)
18
Environment
Protective treatment
TC
Ambient air temperature for storage
-40…70 °C
Ambient air temperature for operation
-25…70 °C
Electrical shock protection class
Class I conforming to IEC 60536
IP degree of protection
IP54 conforming to IEC 60529
IK degree of protection
IK08 conforming to IEC 62262
Standards
IEC 60947-5-1
Logistical informations
Country of origin
CZ
Main
Range of product
Harmony XAPS
Product or component type
Key operated control station
Device short name
XAPS
Product mounting
Surface mounted
Control station composition
1 key selector switch, spring return from right to left 1 NO right arrow marking
Operator position information
2 positions
Key withdrawal position
Left-hand
Contact operation
Slow-break
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.300 cm
Package 1 Width
10.500 cm
Package 1 Length
11.000 cm
Package 1 Weight
453.000 g
Unit Type of Package 2
S01
Number of Units in Package 2
6
Package 2 Height
15.000 cm
Package 2 Width
15.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
2.919 kg
Metal housing for Harmony XB4 The XAM and XAP M surface-mounted housings are suitable for a wide range of applications. Both the robust zinc injection-molded housings and the ergonomically shaped angled housings are available. Installation plates made of aluminum round off the range.