Further information for Schneider Electric XALD363G enclosure 2 push buttons 1 indicator light green red
Complementary
AC control voltage 50 HZ
120 V
Cable entry
2 knock-outs for cable entry, clamping capacity: 14 mm; 2 knock-outs for Pg 13 cable gland and ISO M20, clamping capacity: 12 mm
AC control voltage 60 HZ
120 V
Net weight
0.261 kg
DC control voltage
125…600 V
Resistance to high pressure washer
7000000 Pa at 55 °C, distance : 0.1 m
Number of command positions
2
Number of indicator lights
1
Colour of marking
Black marking when white caps; White marking when green, red or black caps
Number of push buttons
2
Positive opening
With conforming to IEC 60947-5-1 appendix K
Operating travel
1.5 mm (NC changing electrical state); 2.6 mm (NO changing electrical state); 4.3 mm (total travel)
Operating force
3.5 N NC changing electrical state; 3.8 N NO changing electrical state
Mechanical durability
10000000 cycles
Number of selector switches
0
Connections - terminals
Screw clamp terminals, = 1 x 0.22 mm² without cable end conforming to IEC 60947-1
Tightening torque
0.8…1.2 N.m conforming to IEC 60947-1
Number of key switches
0
Shape of screw head
Cross compatible with Philips no 1 screwdriver; Cross compatible with pozidriv No 1 screwdriver; Slotted compatible with flat Ø 4 mm screwdriver; Slotted compatible with flat Ø 5.5 mm screwdriver
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
10 A cartridge fuse type gG conforming to IEC 60947-5-1
[Ith] conventional free air thermal current
10 A conforming to IEC 60947-5-1
[Ui] rated insulation voltage
600 V (pollution degree 3) conforming to IEC 60947-1
Number of mushroom-shaped push-buttons
0
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
[Ie] rated operational current
6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1; 3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1; 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1; 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1; 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1
Electrical durability
1000000 cycles, AC-15, 2 A at 230 V, operating rate
Electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA conforming to IEC 60947-5-4; Λ < 10exp(-8) at 17 V, 5 mA conforming to IEC 60947-5-4
Signalling type
Steady
Current consumption
14 mA
Number of contacts as normally closed contact
1
Service life
100000 h at rated voltage and 25 °C
Surge withstand
1 kV conforming to IEC 61000-4-5
Number of contacts as normally open contact
1
Number of contacts as change-over contact
0
Housing material
Plastic
Housing colour
Grey
Emergency power off
Contractual warranty
Warranty (in months)
18
Environment
Protective treatment
TH
Ambient air temperature for storage
-40…70 °C
Ambient air temperature for operation
-40…70 °C
Overvoltage category
Class II conforming to IEC 60536
IP degree of protection
IP66 conforming to IEC 60529; IP67; IP69; IP69K
NEMA degree of protection
NEMA 13; NEMA 4X
IK degree of protection
IK05 conforming to IEC 62262
Standards
UL 508; IEC 60947-1; IEC 60947-5-4; JIS C8201-5-1; IEC 60947-5-1; IEC 60947-5-5; CSA C22.2 No 14; JIS C8201-1
Vibration resistance
5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Resistance to fast transients
2 kV conforming to IEC 61000-4-4
Resistance to electromagnetic fields
10 V/m conforming to IEC 61000-4-3
Resistance to electrostatic discharge
6 kV on contact (on metal parts) conforming to IEC 61000-4-2; 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2
Electromagnetic emission
Class B conforming to IEC 55011
Logistical informations
Country of origin
FR
Main
Range of product
Harmony XALD
Product or component type
Complete control station
Device short name
XALD
Product destination
For XB5 Ø 22 mm control and signalling units
Control station application
Start-Stop function
Colour of base of enclosure
Light grey (RAL 7035)
Colour of cover
Dark grey (RAL 7016)
Material
Polycarbonate
Operator profile
2 flush push-buttons - 1 central pilot light
Operators description
Green ''I'' 1 NO - red ''O'' 1 NC
Control station composition
1 flush push-button, green 1 NO I marking; 1 flush push-button, red 1 NC O marking; 1 pilot light
Marking location
Marking on push-button
Contact operation
Slow-break
Light source
Integrated and protected LED
Light source colour
Red
[Us] rated supply voltage
120 V AC
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.300 cm
Package 1 Width
6.800 cm
Package 1 Length
13.600 cm
Package 1 Weight
261.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
20
Package 2 Height
30 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
6.264 kg
The plastic surface-mounted housings of the Harmony XALD series are available both as complete housings for direct use and as empty housings for individual assembly. The robust plastic housings made of polycarbonate are ideal for universal use in industry and mechanical engineering. This surface-mounted housing in dark gray has 2 holes of 22mm and is already factory-fitted with 2 push buttons with 1 NO contact and 1 NC contact. The auxiliary switches can also be flexibly selected between front and base mounting. This complete housing is therefore ideally suited for direct use. Suitable for international use due to the large number of existing product standards and certifications. Thanks to the Green Premium environmental label, you can receive detailed information on material content, environmental impact and circular economy that supports your sustainability goals.