| Complementary |
| Electrical connection | Terminal |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Net weight | 75 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP00 |
| Pollution degree | 2 conforming to EN 50178 |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -10…45 °C |
| Ambient air temperature for storage | -40…65 °C |
| Standards | UL 508 |
| Logistical informations |
| Country of origin | CN |
| Main |
| Product or component type | Sinus filter |
| Range compatibility | Altivar Process ATV600; Altivar Process ATV900 |
| Product specific application | Output filter |
| [In] rated current | 75 A |
| Thermal losses | 500 W, 115 °C |
| Switching frequency | 2 kHz |
| Maximum output frequency | 70 Hz |
| maximum permissible voltage | 690 V AC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 60.0 cm |
| Package 1 Width | 56.6 cm |
| Package 1 Length | 69.6 cm |
| Package 1 Weight | 100.0 kg |
This product is a sinusoidal output filter from the manufacturer Schneider Electric, type VW3A5218, specifically designed for frequency converters of the Altivar Process ATV600 and ATV900 product families. It serves as an output filter to reduce voltage ripple at the output of the frequency converter, thereby delivering a sinusoidal voltage to the connected motor. This is particularly important in applications where high requirements exist for power quality and the service life of drive technology. The filter is rated for a nominal current of 75 A and supports a maximum voltage of 690 V AC. The maximum output frequency is 70 Hz, with the filter's switching frequency set at 2 kHz. The device's thermal losses amount to 500 W at a maximum temperature of 115 °C.
Applications
The sinus filter is used in industrial drive systems where frequency converters operate under high demands for power quality. It is particularly suitable for applications where the motor winding could be stressed by high voltage peaks or high-frequency components, for example in process engineering, the paper industry, or conveyor systems. Using the filter reduces electromagnetic compatibility (EMC) interference and extends the motor's service life.
Functions and Equipment in Detail
The filter is designed as an output filter to be installed directly at the output of the frequency converter. It ensures a clean, sinusoidal voltage at the motor connection, thereby reducing motor stress. Electrical connections are made via terminals, enabling simple and secure installation. The filter can handle a maximum current of 1.5 times the rated current (75 A) for up to 60 seconds, making it suitable for short-term load peaks.
Technology Explained Simply
A sinus filter reduces the high-frequency components generated by the PWM operation of a frequency converter. These high frequencies can lead to increased motor heating, additional losses, and EMC issues. The filter smooths the voltage waveform and delivers a nearly sinusoidal voltage to the motor. The switching frequency of 2 kHz is crucial for the filter's performance, as it effectively suppresses frequency components above this threshold. The maximum output frequency of 70 Hz allows operation at high speeds without impairing the filter function.
Compatibility and Accessories
The filter is specifically designed for frequency converters from the Altivar Process ATV600 and ATV900 product families. It is not suitable for other frequency converters unless their technical specifications match.
Mounting and Installation
Installation is carried out directly at the output of the frequency converter. The protection rating IP00 means the device is not protected against mechanical impacts or environmental conditions such as dust or water. Therefore, it must be installed in enclosed, dry, and dust-free rooms. Pollution degree class 2 corresponds to standard EN 50178 and is suitable for environments with low pollution. The operating temperature ranges from -10 °C to 45 °C, and the storage temperature ranges from -40 °C to 65 °C. The operating altitude is up to 1,000 m without current derating; from 1,000 m to 3,000 m, a current derating of 1 % per 100 m is required. The relative humidity must not exceed 95 %. Vibration test resistance is 1 Gn at frequencies from 13 to 200 Hz and 1.5 mm peak-to-peak at 3 to 13 Hz, according to IEC 60068-2. Shock resistance is 15 Gn for 11 ms, according to IEC 60068-2-27.
Operational Advantages
Using the sinus filter improves power quality at the motor connection, extending motor life and reducing maintenance costs. The reduction in electromagnetic compatibility (EMC) interference minimizes disturbances in the surrounding environment. The robust construction and high thermal load capacity make the filter suitable for industrial applications. Conformity with UL 508 ensures the safety and reliability of the device.