| Complementary |
| Electrical connection | Terminal 50 mm² 1/0 AWG |
| maximum earth leakage current | 13.9 mA at 400 V 50 Hz TN; 13.9 mA at 400 V 50 Hz TT |
| power supply voltage | 380…480 V; 200…240 V |
| Tolerance | 10 % |
| Mechanical robustness | Shocks class 3M4 conforming to IEC 60721-3-3; Vibrations class 3M4 conforming to IEC 60721-3-3 |
| Width | 120 mm |
| Height | 340 mm |
| Depth | 180 mm |
| Net weight | 6.5 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20mounting side by side; IP21with kit VW3A47906 |
| Relative humidity | 5…95 % without condensation conforming to IEC 61800-5-1 |
| Ambient air temperature for operation | -10…50 °C (without current derating); 50…60 °C (with current derating 1.5 % per °C) |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 0...1000 m without current derating; 1000...4000 m with current derating 1 % per 100 m |
| Standards | IEC 61800-3 |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | Altivar |
| Product or component type | EMC input filter |
| Range compatibility | Altivar Machine ATV340; Altivar Process ATV600; Altivar Process ATV900 |
| Product specific application | Radio interference input filter |
| Mounting location | At variable speed drive side |
| [In] rated current | 100 A |
| Thermal losses | 12.4 W |
| Network number of phases | Three phase |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 28.500 cm |
| Package 1 Width | 37.500 cm |
| Package 1 Length | 53.000 cm |
| Package 1 Weight | 11.179 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 58.248 kg |
Three-phase supply voltage 200-240 V 50 Hz. EMC radio interference suppression filter, for frequency converter, for ATV630D18M3 - D22M3 converter, category C3, 100 m. Filter_rated current 13.9 mA. The max. lengths are only examples, as they vary according to the stray capacitance of the motors and cables used. For motors connected in parallel, the length of all cables must be taken into account. The values indicated depend on the nominal switching frequency of the converter. This frequency depends on the nominal size of the converter. Max. length of the shielded cable according to IEC/EN 61800-3 category C2 (50m). Max. length of the shielded cable according to IEC/EN 61800-3 category C3. For more stringent requirements, additional EMC input filters can be used. They reduce conducted emissions to values below category C1, C2 or C3 of the IEC/EN 61800-3 standard. These additional filters can only be used in TN networks (connection to neutral conductor) or TT networks (connection of the neutral conductor to earth). According to the IEC/EN 61800-3 standard, Appendix D2.1, filters in IT systems (isolated or neutral earthed impedance) can result in continuous insulation monitoring only taking place in random operation.