| Complementary |
| Range compatibility | Altivar 61; Altivar Process ATV900; Altivar 71; Altivar Process ATV600 |
| [Us] rated supply voltage | 400 V +/- 10 % |
| Supply frequency | 50 Hz +/- 2 % |
| [In] rated current | 144 A for input; 150 A for output |
| Network number of phases | 3 phases |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Efficiency | 98 % |
| Thermal losses | 962 W |
| Cos phi | 1 (150 % of line current); 0.85 (75 % of line current); 0.99 (100 % of line current) |
| Electrical connection | A, B terminal, connection capacity: 2.5 mm²; X1-1...X2-3 terminal, connection capacity: 2.5...90 mm² |
| Electrical insulation class | Class F |
| Net weight | 126 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20; IP55 (enclosure mounting) |
| Vibration resistance | 2 mm peak to peak (f= 5…13.2 Hz) conforming to IEC 60068-2-6; 0.7 gn (f= 13.2…150 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 5…85 % without condensation |
| Ambient air temperature for operation | 45…60 °C (with current derating 3 % per °C); 5…45 °C (without current derating) |
| Ambient air temperature for storage | -25…55 °C storage in original packaging; -25…65 °C during transport |
| Operating altitude | 1000...4000 m with current derating 5 % per 1000 m |
| Standards | IEC 61000-2-4; IEC 61000-2-2; G5/4 engineering recommendation; IEC 61000-3-4; IEC 61000-3-12; IEC 61000-3-2 |
| Logistical informations |
| Country of origin | DE |
| Main |
| Product or component type | Passive filter |
| Product specific application | Reduction of current harmonics |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 61.000 cm |
| Package 1 Width | 60.000 cm |
| Package 1 Length | 80.000 cm |
| Package 1 Weight | 138.2 kg |
Passive filter power supply 400 V, 50 Hz, three-phase. For frequency converter, use for ATV630D75N4, ATV650D75N4, ATV650D75N4E. Filter operating current output 150 A, filter operating current input 144 A, power KW 100 HP. Quantity per converter 1 time. THDI < 5%. If the filter is used with ATV650U07N4/N4E - D90N4/N4E converters, it must be installed in a separate cabinet to ensure protection class IP 55.