| Complementary |
| Range compatibility | Altivar Process ATV900; Altivar Process ATV600; Altivar 71; Altivar 61 |
| [Us] rated supply voltage | 400 V +/- 10 % |
| Supply frequency | 50 Hz +/- 2 % |
| [In] rated current | 29 A for input; 30 A for output |
| Network number of phases | 3 phases |
| THDI | 10 % for variable speed drive ATV61H motor: 15 kW/20 hp; 10 % for variable speed drive ATV71H motor: 15 kW/20 hp; 10 % for variable speed drive ATV71W motor: 15 kW/20 hp; 5 % for variable speed drive ATV61W motor: 15 kW/20 hp; 5 % for variable speed drive ATV650 motor: 15 kW/20 hp; 5 % for variable speed drive ATV630 motor: 15 kW/20 hp; 5 % for variable speed drive ATV950 motor: 15 kW/20 hp; 5 % for variable speed drive ATV930 motor: 15 kW/20 hp |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Efficiency | 98 % |
| Thermal losses | 298 W |
| Cos phi | 1 (150 % of line current); 0.85 (75 % of line current); 0.99 (100 % of line current) |
| Electrical connection | X1-1...X2-3 terminal, connection capacity: 0.5...10 mm²; A, B terminal, connection capacity: 2.5 mm² |
| Electrical insulation class | Class F |
| Net weight | 34 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20; IP55 (enclosure mounting) |
| Vibration resistance | 2 mm peak to peak (f= 5…13.2 Hz) conforming to IEC 60068-2-6; 0.7 gn (f= 13.2…150 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 5…85 % without condensation |
| Ambient air temperature for operation | 45…60 °C (with current derating 3 % per °C); 5…45 °C (without current derating) |
| Ambient air temperature for storage | -25…55 °C storage in original packaging; -25…65 °C during transport |
| Operating altitude | 1000...4000 m with current derating 5 % per 1000 m |
| Standards | G5/4 engineering recommendation; IEC 61000-2-4; IEC 61000-3-12; IEC 61000-2-2; IEC 61000-3-2; IEC 61000-3-4 |
| Logistical informations |
| Country of origin | DE |
| Main |
| Product or component type | Passive filter |
| Product specific application | Reduction of current harmonics |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 56.0 cm |
| Package 1 Width | 40.0 cm |
| Package 1 Length | 60.0 cm |
| Package 1 Weight | 41.5 kg |
Passive Filter Spannungsversorgung 400 V, 50 Hz, dreiphasig. Für Frequenzumrichter, Verwendung für ATV630D15N4, ATV650D15N4, ATV650D15N4E. Filter_Betriebsstrom_Ausgang 30 A, Filter_Betriebsstrom_Eingang 29 A, Leistung KW 20 PS. Anzahl pro Umrichter 1 mal. THDI < 5 %. Wenn der Filter mit ATV650U07N4/N4E - D90N4/N4E Umrichtern verwendet wird, muss er in einen separaten Schrank verbaut werden, um die Schutzart IP 55 zu gewährleisten.