| Complementary |
| Range compatibility | Altivar Process ATV900; Altivar Process ATV600; Altivar 61; Altivar 71 |
| [Us] rated supply voltage | 400 V +/- 10 % |
| Supply frequency | 50 Hz +/- 2 % |
| [In] rated current | 180 A for input; 187 A for output |
| Network number of phases | 3 phases |
| THDI | 10 % for variable speed drive ATV61H motor: 110 kW/150 hp; 10 % for variable speed drive ATV71H motor: 110 kW/150 hp; 10 % for variable speed drive ATV61Q motor: 110 kW/150 hp; 10 % for variable speed drive ATV71Q motor: 110 kW/150 hp; 10 % for variable speed drive ATV650 motor: 90 kW/125 hp; 10 % for variable speed drive ATV630 motor: 90 kW/125 hp; 10 % for variable speed drive ATV950 motor: 90 kW/125 hp; 10 % for variable speed drive ATV930 motor: 90 kW/125 hp |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Efficiency | 98 % |
| Thermal losses | 743 W |
| Cos phi | 1 (150 % of line current); 0.85 (75 % of line current); 0.99 (100 % of line current) |
| Electrical connection | A, B terminal, connection capacity: 2.5 mm²; X1-1...X2-3 terminal, connection capacity: 2.5...90 mm² |
| Electrical insulation class | Class F |
| Net weight | 102 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20; IP55 (enclosure mounting) |
| Vibration resistance | 2 mm peak to peak (f= 5…13.2 Hz) conforming to IEC 60068-2-6; 0.7 gn (f= 13.2…150 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 5…85 % without condensation |
| Ambient air temperature for operation | 45…60 °C (with current derating 3 % per °C); 5…45 °C (without current derating) |
| Ambient air temperature for storage | -25…55 °C storage in original packaging; -25…65 °C during transport |
| Operating altitude | 1000...4000 m with current derating 5 % per 1000 m |
| Standards | G5/4 engineering recommendation; IEC 61000-3-12; IEC 61000-3-4; IEC 61000-2-2; IEC 61000-3-2; IEC 61000-2-4 |
| Main |
| Product or component type | Passive filter |
| Product specific application | Reduction of current harmonics |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 61.000 cm |
| Package 1 Width | 60.000 cm |
| Package 1 Length | 80.000 cm |
| Package 1 Weight | 114.2 kg |
Passive filter power supply 400 V, 50 Hz, three-phase. For frequency converter, use for ATV630D90N4, ATV650D90N4, ATV650D90N4E. Filter operating current output 187 A, filter operating current input 180 A, power KW 90 kW, power HP 125 HP. Quantity per converter 1 time. THDI < 10%. If the filter is used with ATV650U07N4/N4E - D90N4/N4E converters, it must be installed in a separate cabinet to ensure protection class IP 55.