| Complementary |
| Range compatibility | Altivar Process ATV600; Altivar Process ATV900; Altivar 61; Altivar 71 |
| [Us] rated supply voltage | 400 V +/- 10 % |
| Supply frequency | 50 Hz +/- 2 % |
| [In] rated current | 101 A for input; 105 A for output |
| Network number of phases | 3 phases |
| THDI | 10 % for variable speed drive ATV61W motor: 55 kW/75 hp; 16 % for variable speed drive ATV61H motor: 55 kW/75 hp; 16 % for variable speed drive ATV71H motor: 55 kW/75 hp; 16 % for variable speed drive ATV71W motor: 55 kW/75 hp; 10 % for variable speed drive ATV650 motor: 55 kW/75 hp; 10 % for variable speed drive ATV630 motor: 55 kW/75 hp; 10 % for variable speed drive ATV950 motor: 55 kW/75 hp; 10 % for variable speed drive ATV930 motor: 55 kW/75 hp |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Efficiency | 98 % |
| Thermal losses | 488 W |
| Cos phi | 1 (150 % of line current); 0.85 (75 % of line current); 0.99 (100 % of line current) |
| Electrical connection | A, B terminal, connection capacity: 2.5 mm²; X1-1...X2-3 terminal, connection capacity: 10...70 mm² |
| Electrical insulation class | Class F |
| Net weight | 74 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20; IP55 (enclosure mounting) |
| Vibration resistance | 2 mm peak to peak (f= 5…13.2 Hz) conforming to IEC 60068-2-6; 0.7 gn (f= 13.2…150 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 5…85 % without condensation |
| Ambient air temperature for operation | 45…60 °C (with current derating 3 % per °C); 5…45 °C (without current derating) |
| Ambient air temperature for storage | -25…55 °C storage in original packaging; -25…65 °C during transport |
| Operating altitude | 1000...4000 m with current derating 5 % per 1000 m |
| Standards | IEC 61000-3-4; IEC 61000-3-2; IEC 61000-3-12; IEC 61000-2-2; G5/4 engineering recommendation; IEC 61000-2-4 |
| Logistical informations |
| Country of origin | DE |
| Main |
| Product or component type | Passive filter |
| Product specific application | Reduction of current harmonics |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 62.000 cm |
| Package 1 Width | 60.000 cm |
| Package 1 Length | 80.000 cm |
| Package 1 Weight | 79.000 kg |
Passive filter power supply 400 V, 50 Hz, three-phase. For frequency converter, use for ATV630D55N4, ATV650D55N4, ATV650D55N4E. Filter operating current output 105 A, filter operating current input 101 A, power KW 55 kW, power HP 75 HP. Quantity per converter 1 time. THDI < 10%. If the filter is used with ATV650U07N4/N4E - D90N4/N4E converters, it must be installed in a separate cabinet to ensure protection class IP 55.