| Complementary |
| power supply frequency | 50...60 Hz |
| Max current | 1.65 x nominal current (duration = 60 s) |
| Maximum voltage drop at rated load | 5 % |
| Electrical insulation class | Class F |
| Minimum clearance distance | 5.5 mm IEC 60664 |
| Leakage distance | 11.5 mm conforming to IEC 60664 |
| Net weight | 11 kg |
| Width | 180 mm |
| Height | 210 mm |
| Depth | 165 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 50178; IEC 60076 (with HD398); VDE 0160 level 1 |
| IP degree of protection | Choke: IP00; Terminals: IP10 |
| Environmental characteristic | 3B1 conforming to IEC 721-3-3; 3C2 conforming to IEC 721-3-3; 3S1 conforming to IEC 721-3-3 |
| Pollution degree | 2 conforming to EN 50178 |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | 45…55 °C (with current derating of 2 % per °C); 0…45 °C (without current derating) |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range of product | Altivar |
| Product or component type | Line/motor choke |
| number of phases | Three phase |
| Range compatibility | Altivar 32; Altivar Machine ATV340; Lexium 62; Altivar 71; Altivar Machine ATV320; Altivar 312; Altivar Process ATV900; Altivar Process ATV600; Altivar 61; Lexium 32; Easy Altivar 310 |
| Device application | Reduction of overvoltages at motor terminals; Reduction of current harmonics |
| Value of inductance | 0.5 mH |
| [In] rated current | 60 A |
| Thermal losses | 94 W |
| Electrical connection | Terminal 35 mm² / 0 AWG, 2.5…3 N.m |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 25.000 cm |
| Package 1 Width | 29.500 cm |
| Package 1 Length | 31.000 cm |
| Package 1 Weight | 11.594 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 59.500 kg |
This line choke is an option for variable speed drives of the Altivar range. Its nominal current is equal to 60A. It provides improved protection against overvoltages on the mains supply and helps reduce the harmonic distortion of the current generated by the inverter. Its degree of protection is IP00. It has an inductance value of 0.5 mH. It weighs 11 kg and has the following dimensions: 180 mm wide, 210 mm high, 165 mm deep. Its use is particularly recommended in cases of close parallel connection of several inverters, in cases of mains supply with significant disturbances from other equipment (interference, overvoltages). As well as in cases of mains supply with voltage imbalance between the phases.