| Complementary |
| power supply frequency | 50...60 Hz |
| Max current | 1.65 x nominal current (duration = 60 s) |
| Maximum voltage drop at rated load | 5 % |
| Electrical insulation class | Class F |
| Minimum clearance distance | 5.5 mm IEC 60664 |
| Leakage distance | 11.5 mm conforming to IEC 60664 |
| Net weight | 3 kg |
| Width | 130 mm |
| Height | 155 mm |
| Depth | 90 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 50178; IEC 60076 (with HD398); VDE 0160 level 1 |
| IP degree of protection | Choke: IP00; Terminals: IP20 |
| Environmental characteristic | 3B1 conforming to IEC 721-3-3; 3C2 conforming to IEC 721-3-3; 3S1 conforming to IEC 721-3-3 |
| Pollution degree | 2 conforming to EN 50178 |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | 45…55 °C (with current derating of 2 % per °C); 0…45 °C (without current derating) |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range of product | Altivar |
| Product or component type | Line/motor choke |
| number of phases | Three phase |
| Range compatibility | Altivar 61; Altivar 312 Solar; Altivar 32; Altivar Process ATV600; Altivar 31C; Lexium 05; Altivar 71; Altivar Machine ATV340; Altivar Machine ATV320; Easy Altivar 310; Altivar 12; Lexium 62; Altivar Process ATV900; Altivar 312; Easy Altivar 310L |
| Device application | Reduction of current harmonics; Reduction of overvoltages at motor terminals |
| Value of inductance | 4 mH |
| [In] rated current | 10 A |
| Thermal losses | 65 W |
| Electrical connection | Terminal 2.5 mm² / 12 AWG, 0.4…0.6 N.m |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 18.000 cm |
| Package 1 Width | 24.500 cm |
| Package 1 Length | 25.500 cm |
| Package 1 Weight | 3.431 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 18 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 74.758 kg |
This line choke is an option for variable speed drives of the Altivar range. Its nominal current is equal to 10A. It provides improved protection against overvoltages on the mains supply and helps reduce the harmonic distortion of the current generated by the inverter. Its degree of protection is IP00. It has an inductance value of 4mH. It weighs 3 kg and has the following dimensions: 130 mm wide, 155 mm high, 90 mm deep. Its use is particularly recommended in cases of close parallel connection of several inverters, in cases of mains supply with significant disturbances from other equipment (interference, overvoltages). As well as in cases of mains supply with voltage imbalance between the phases.