| Complementary |
| power supply frequency | 50...60 Hz |
| Max current | 1.65 x nominal current (duration = 60 s) |
| Maximum voltage drop at rated load | 5 % |
| Electrical insulation class | Class F |
| Minimum clearance distance | 5.5 mm IEC 60664 |
| Leakage distance | 11.5 mm conforming to IEC 60664 |
| Net weight | 1.5 kg |
| Width | 100 mm |
| Height | 135 mm |
| Depth | 60 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | VDE 0160 level 1; IEC 60076 (with HD398); EN 50178 |
| IP degree of protection | Choke: IP00; Terminals: IP20 |
| Environmental characteristic | 3B1 conforming to IEC 721-3-3; 3C2 conforming to IEC 721-3-3; 3S1 conforming to IEC 721-3-3 |
| Pollution degree | 2 conforming to EN 50178 |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | 45…55 °C (with current derating of 2 % per °C); 0…45 °C (without current derating) |
| Ambient air temperature for storage | -25…70 °C |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range of product | Altivar |
| Product or component type | Line/motor choke |
| number of phases | Three phase |
| Range compatibility | Altivar 61; Altivar 312; Altivar Process ATV900; Altivar 32; Altivar 312 Solar; Altivar Process ATV600; Altivar 31C; Lexium 62; Easy Altivar 310; Altivar Machine ATV340; Altivar Machine ATV320; Altivar 71; Altivar 12; Easy Altivar 310L |
| Device application | Reduction of current harmonics |
| Value of inductance | 10 mH |
| [In] rated current | 4 A |
| Thermal losses | 45 W |
| Electrical connection | Terminal 2.5 mm² / 12 AWG, 0.4…0.6 N.m |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.500 cm |
| Package 1 Width | 18.500 cm |
| Package 1 Length | 21.000 cm |
| Package 1 Weight | 1.598 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 48.352 kg |
This line choke is an option for variable speed drives of the Altivar range. Its nominal current is equal to 4A. It provides improved protection against overvoltages on the mains supply and helps reduce the harmonic distortion of the current generated by the inverter. Its degree of protection is IP00. It has an inductance of 10mH. It weighs 1.5 kg and has the following dimensions: 100 mm wide, 135 mm high, 60 mm deep. Its use is particularly recommended when several inverters are connected in close parallel, when the mains supply is subject to significant disturbances from other equipment (interference, overvoltages). As well as when the mains supply has voltage imbalance between the phases.