| Complementary |
| Electrical connection | Terminal 50 mm² 0 AWG |
| Tightening torque | 6 N.m |
| maximum earth leakage current | 60 mA at 400 V 50 Hz; 106 mA at 480 V 60 Hz |
| power supply voltage | 200…240 V; 380…500 V |
| Tolerance | 10 % |
| Net weight | 17 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20; IP41 (upper part) |
| Relative humidity | 0…93 % conforming to IEC 68-2-3 |
| Ambient air temperature for operation | -10…50 °C |
| Ambient air temperature for storage | -40…65 °C |
| Vibration resistance | 1 gn (f= 13…150 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Standards | IEC 61800-3 |
| Logistical informations |
| Country of origin | TH |
| Main |
| Range of product | Altivar |
| Product or component type | EMC input filter |
| Range compatibility | Altivar 61; Altivar 71; Altivar 212 |
| Product compatibility | ATV212HD37N4; ATV212HD45N4; ATV21HD37N4; ATV21HD45N4; ATV61HD30N4; ATV61HD37N4; ATV71HD30N4; ATV71HD37N4; ATV71WD30N4; ATV71WD37N4 |
| Product specific application | Radio interference input filter |
| [In] rated current | 92 A |
| Thermal losses | 16 W for ATV21HD37N4; 23 W for ATV21HD45N4; 30 W |
| Network number of phases | Three phase |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 20.000 cm |
| Package 1 Width | 91.000 cm |
| Package 1 Length | 48.000 cm |
| Package 1 Weight | 15.166 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 54.000 kg |
This EMC filter is an option for Altivar series variable speed drives and Lexium series servo drives. Its nominal current is 92A. It is used to reduce conducted emissions on the mains supply to below the limits of EN 55011 Group 1, Class A or B and IEC/EN 61800-3 Category C1, C2. Its degree of protection is IP20. It weighs 17 kg. This additional EMC filter can only be used on TN (neutral connection) and TT (earthed neutral) type systems.