| Complementary |
| Number of step output contacts | 12 |
| [Us] rated supply voltage | 90...550 V AC; |
| Measurement current | 0…5 A |
| Measurement voltage | 90…550 V AC 50/60 Hz |
| Operating mode | Manual or automatic |
| Number of quadrant operation for generator application | 4 |
| Device connection | Communication protocol: Modbus interface: RS485 |
| Input function | Switch: 1 x dry contact |
| Colour code | Front: dark grey RAL 7016 |
| Display type | Backlit LCD |
| Display size | 56 x 25 mm |
| Function available | Manual programming; Automatic initialisation; Automatic detection; Advanced programming (expert); Any step sequence |
| Metering type | Power factor and displacement PF (signed, four quadrant); Total current harmonic distortion THD (I); Power factor average over lifetime; Temperature maximum; Phase current I1, I2, I3 RMS on load; Active power P, P1, P2, P3 on load; Reactive power Q, Q1, Q2, Q3 on load; Apparent power S, S1, S2, S3 on load; Voltage U21, U32, U13, V1, V2, V3 on load |
| Type of measurement | Capacitor current overload Irms/I1; Individual voltage harmonic; Power factor; Operating time; Cos φ; Ambient temperature inside the cubicle; Tan φ |
| Information displayed | Number of switching cycles per step; Individual step size in kVAr; Remaining step capacity in % |
| Data recording | 5 alarms |
| Operational Hours alarm | 100000 h without maintenance |
| Operational counter alarm | 65000 cycles without maintenance |
| Input type | Phase to phase; Phase to neutral; Insensitive to CT polarity; Insensitive to phase rotation polarity; Current input CT...X/5 A and X/1 A |
| Output type | Control relay: 0.2 A 110 V DC; Control relay: 1 A 48 V DC; Control relay: 2 A 400 V AC 50/60 Hz; Control relay: 1 A 24 V DC; Control relay: 5 A 250 V AC 50/60 Hz; Control relay: 5 A 120 V AC 50/60 Hz; Fan: 5 A 250 V AC 50/60 Hz; Fan: 1 A 48 V DC; Alarm relay: 5 A 250 V AC 50/60 Hz; Alarm relay: 1 A 48 V DC |
| Maximum at the common terminal | 10 A |
| Settings operating mode | Automatic; Manual |
| Type of setting | Choice of stepping programs: auto; Choice of stepping programs: LIFO; Choice of stepping programs: linear; Delay between 2 successive switch on the same step: 5...1200 s; Step configuration programming: auto; Step configuration programming: off; Step configuration programming: fixed; Target cos phi: 0.7 inductive...0.7 capacitive; Target cos phi: dual cos φ |
| Measurement accuracy | Voltage +/- 1 %; Current +/- 1 %; Frequency +/- 1 %; Energy (P,Q,S) +/- 2 %; Cos φ +/- 2 %; Total voltage harmonic distortion THD (U) +/- 2 %; Individual voltage harmonic +/- 3 %; Temperature +/- 3 °C |
| Time delay range | 1...6500 s (on reconnection); 1...6500 s (on response) |
| Provided equipment | User manual |
| Mounting mode | Flush-mounted |
| Mounting support | Panel - thickness: 1…3 mm |
| Mounting location | In cabinet |
| Cut-out dimensions | 138 x 138 mm |
| Height | 144 mm |
| Width | 144 mm |
| Depth | 58 mm |
| Net weight | 0.6 kg |
| Compatibility code | VPL 12 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 61000-6-4; UL 61010-1; EN 61010-1; IEC 61000-6-2; IEC 61326-1 |
| Product certifications | EAC; NRTL; cNRTL; CE |
| IP degree of protection | Front face: IP41; Rear face: IP20 |
| Ambient air temperature for operation | -20…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | DE |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PFC Controller |
| Product or component type | Power factor controller |
| Device short name | VPL12 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.200 cm |
| Package 1 Width | 17.700 cm |
| Package 1 Length | 18.400 cm |
| Package 1 Weight | 727.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.155 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 64 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 58.408 kg |
The PowerLogic PFC Controller is a simple and efficient reactive power controller for an automatic reactive power compensation system to maintain the reactive power factor. It is a simple and intelligent controller for measuring, monitoring and controlling reactive energy. It has easy commissioning, step size detection and monitoring, and various alarms. VPL12 can be used for 12 steps in a PFC system.