| Complementary |
| Number of step output contacts | 6 |
| [Us] rated supply voltage | 90...550 V AC; |
| Measurement current | 0…5 A |
| Measurement voltage | 90…550 V AC 50/60 Hz |
| Operating mode | Manual or automatic |
| Number of quadrant operation for generator application | 4 |
| Device connection | Communication protocol: Modbus interface: RS485 |
| Input function | Switch: 1 x dry contact |
| Colour code | Front: dark grey RAL 7016 |
| Display type | Backlit LCD |
| Display size | 56 x 25 mm |
| Function available | Automatic detection; Advanced programming (expert); Manual programming; Any step sequence; Automatic initialisation |
| Metering type | Power factor and displacement PF (signed, four quadrant); Total current harmonic distortion THD (I); Power factor average over lifetime; Temperature maximum; Phase current I1, I2, I3 RMS on load; Active power P, P1, P2, P3 on load; Reactive power Q, Q1, Q2, Q3 on load; Apparent power S, S1, S2, S3 on load; Voltage U21, U32, U13, V1, V2, V3 on load |
| Type of measurement | Ambient temperature inside the cubicle; Tan φ; Individual voltage harmonic; Cos φ; Operating time; Power factor; Capacitor current overload Irms/I1 |
| Information displayed | Number of switching cycles per step; Remaining step capacity in %; Individual step size in kVAr |
| Data recording | 5 alarms |
| Operational Hours alarm | 100000 h without maintenance |
| Operational counter alarm | 65000 cycles without maintenance |
| Input type | Insensitive to phase rotation polarity; Insensitive to CT polarity; Phase to neutral; Current input CT...X/5 A and X/1 A; Phase to phase |
| Output type | Control relay: 0.2 A 110 V DC; Control relay: 1 A 48 V DC; Control relay: 2 A 400 V AC 50/60 Hz; Control relay: 1 A 24 V DC; Control relay: 5 A 250 V AC 50/60 Hz; Control relay: 5 A 120 V AC 50/60 Hz; Fan: 5 A 250 V AC 50/60 Hz; Fan: 1 A 48 V DC; Alarm relay: 5 A 250 V AC 50/60 Hz; Alarm relay: 1 A 48 V DC |
| Maximum at the common terminal | 10 A |
| Settings operating mode | Manual; Automatic |
| Type of setting | Choice of stepping programs: auto; Choice of stepping programs: LIFO; Choice of stepping programs: linear; Delay between 2 successive switch on the same step: 5...1200 s; Step configuration programming: auto; Step configuration programming: off; Step configuration programming: fixed; Target cos phi: 0.7 inductive...0.7 capacitive; Target cos phi: dual cos φ |
| Measurement accuracy | Voltage +/- 1 %; Current +/- 1 %; Frequency +/- 1 %; Energy (P,Q,S) +/- 2 %; Cos φ +/- 2 %; Total voltage harmonic distortion THD (U) +/- 2 %; Individual voltage harmonic +/- 3 %; Temperature +/- 3 °C |
| Time delay range | 1...6500 s (on reconnection); 1...6500 s (on response) |
| Provided equipment | User manual |
| Mounting mode | Flush-mounted |
| Mounting support | Panel - thickness: 1…3 mm |
| Mounting location | In cabinet |
| Cut-out dimensions | 138 x 138 mm |
| Height | 144 mm |
| Width | 144 mm |
| Depth | 58 mm |
| Net weight | 0.6 kg |
| Compatibility code | VPL 6 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 61000-6-2; EN 61010-1; IEC 61000-6-4; IEC 61326-1; UL 61010-1 |
| Product certifications | EAC; NRTL; cNRTL; CE |
| IP degree of protection | Front face: IP41; Rear face: IP20 |
| Ambient air temperature for operation | -20…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | DE |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PFC Controller |
| Product or component type | Power factor controller |
| Device short name | VPL6 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.200 cm |
| Package 1 Width | 17.800 cm |
| Package 1 Length | 18.400 cm |
| Package 1 Weight | 696.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.050 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 64 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 60.348 kg |
The PowerLogic PFC Controller is a simple and efficient reactive power controller for an automatic reactive power compensation system to maintain the reactive power factor. It is a simple and intelligent controller for measuring, monitoring and controlling reactive energy. It has easy commissioning, step size detection and monitoring, and various alarms. VPL06 can be used for 6 steps in a PFC system.