| Complementary |
| Network pollution level | Low polluted |
| [Gh/Sn] harmonic pollution rate | 15…25 % |
| [THDU] total harmonic distorsion of voltage | 3…4 % |
| Power per step | 50 kvar |
| Step composition | 2x50 + 5x100 |
| Location of connection | Bottom |
| Controller type | PowerLogic PFC Controller VPL6 |
| capacitor technology | PowerLogic PFC Capacitor |
| Poles description | 3P |
| Capacitance tolerance | - 5 % to 10 % |
| [Ui] rated insulation voltage | 690 V |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Maximum permissible voltage | 1.1 x Un (8 hours over 24 hours) conforming to IEC 60831 |
| [Imp] maximum permanent current | Capacitor: 1.8 x In at 480 V conforming to IEC 60831; Battery: 1.43 x In at 400 V conforming to IEC 61439-2; Battery: 1.19 x In at 415 V conforming to IEC 61439-2 |
| main incomer protection | Without protection |
| [Icw] rated short-time withstand current | 35 kA at 1 s (Icw) |
| Step protection type | Overload: harmonic control from PowerLogic PFC Controller; Short-circuit: fuse |
| Accessibility for operation | Front |
| Colour | Grey (RAL 7035) |
| maximum weight | 434 kg |
| Height | 2200 mm |
| Width | 800 mm |
| Depth | 600 mm |
| Provided equipment | Auxiliary transformer |
| Internal voltage transformer | 400/230 V - 630 VA |
| Function available | GenSet shedding contact; Alarm contact |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 61439-1; IEC 61921; IEC 61439-2 |
| Product certifications | EAC; CE; ASEFA |
| Mounting location | Indoor |
| IP degree of protection | Environment: IP31; Safety: IPxx B |
| IK degree of protection | IK10 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -5…45 °C |
| Average ambient air temperature for operation | 35 °C (annual) ; 45 °C (over 24 hours) |
| Main |
| Network rated voltage | 400 V AC 50 Hz; 415 V AC 50 Hz |
| Reactive power rating | 600 kvar |
| Operating mode | Automatic |
| Range | PowerLogic |
| Device short name | automatic capacitor bank |
| Product or component type | Capacitor bank |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 231.000 cm |
| Package 1 Width | 80.000 cm |
| Package 1 Length | 120.000 cm |
| Package 1 Weight | 335.700 kg |
The low-voltage reactive power compensation from the PowerLogic PFC family helps to avoid contractual penalties from energy suppliers. Save energy, reduce operating costs and reduce CO² emissions through reactive power compensation of inductive loads. This hardware is compatible with the power management software to take advantage of the benefits of digital power supply and enable seamless integration into EcoStruxture Power. Intelligent monitoring and measurement functions are available for safe operation. To optimize operation and maintenance in a wide range of applications, both in commercial and industrial areas. This version, suitable for mains voltage 400V 50Hz, delivers reactive power up to 600kvar. The compensation is automatically set by the reactive power controller of the PowerLogic PFC controller family. It is designed for mains harmonic voltages up to 4% or mains harmonic currents up to 10%, where the grid is defined as a low harmonic load grid. The PowerLogic PFC Capacitor Banks IEC range is certified to CE, IEC 61921, IEC 61439 Part 1 and IEC61439 Part 2. It contains long life capacitors from the PFC capacitor family, designed to IEC831 Part 1 and IEC831 Part 2. And includes an intelligent controller with Modbus communication RS485. The RAL7035 enclosure is a floor standing system with a connection coming from below. The external dimensions of the enclosure are 800mm width, 600mm depth, 2200mm height and a maximum product weight of 434kg. As standard the enclosures are IP31. Optional kits are available to easily convert them to IP54. This product is particularly suitable for reactive power compensation applications with variable or unstable loads.