Further information for Schneider Electric VBD02 load disconnector 690 V black
Complementary
Device Composition
Handle; Switch
Mounting Support
Handle: door; Switch: door
Mounting Method
Hole with 22.5 mm for handle
Performance Level
High performance
Number of Poles
3P
Contact Type and Composition
3 NO
[Ue] IEC Rated Operational Voltage
690 V AC 50/60 Hz
IEC Rated Operational Power in W
3 kW at 400...415 V (AC-3); 4 kW at 500 V (AC-3); 1.5 kW at 230...240 V (AC-3); 5.5 kW at 500 V (AC-23A); 5.5 kW at 690 V (AC-3); 7.5 kW at 690 V (AC-23A); 3 kW at 230...240 V (AC-23A); 4 kW at 400...415 V (AC-23A)
[Ie] Rated Operational Current
8.1 A AC-23 Ue: 400 V
[Ith] Conventional Free Air Thermal Current
12 A
[Ithe] Conventional Enclosed Thermal Current
10 A
Making Capacity ( I Rms)
120 A at 400 V AC-21A; 120 A at 400 V AC-22A; 120 A at 400 V AC-23A
Breaking Capacity
120 A at 400 V (AC-21A); 120 A at 400 V (AC-22A); 120 A at 400 V (AC-23A)
Rated Conditional Short Circuit Current
10 kA at 400 V - associated fuse 12 A aM; 10 kA at 400 V - associated fuse 12 A gG
Power circuit: screw clamp terminals10 mm² - solid; Power circuit: screw clamp terminals6 mm² - flexible - with cable end
Tightening Torque
Power circuit: 2.1 N.m - on screw clamp terminals
Base Dimension
60 x 60 mm
Height
74 mm
Width
60 mm
Product Weight
0.215 kg
Suitability for Isolation
Contractual warranty
Warranty (in months)
18
Environment
Standards
IEC 60947-3
Product Certifications
UL; CCC; GL; CSA; UKCA
Degree of Protection
IP20 conforming to IEC 60529; IP65
Protective Treatment
TC
Mechanical Robustness
Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6; Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Ambient Air Temperature for Operation
-20…50 °C
Fire Resistance
960 °C conforming to IEC 60695-2-1
Compatibility Code
Main switch disconnector
Logistical informations
Country of origin
CZ
Main
Range
TeSys
Product Name
TeSys VARIO
Device Short Name
VBD
Device Application
Preventive maintenance
Product Type
Switch disconnector
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.000 cm
Package 1 Width
8.500 cm
Package 1 Length
12.000 cm
Package 1 Weight
226.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
24
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
5.750 kg
Load break switch VBD, 3, 690 V. Size_A 12 A, mounting diameter 22.5 mm, front plate 60 x 60 mm. Complete device, 3-pole, IP 65, with rotary drive. For mounting in the control cabinet door. Black handle, lockable with 3 padlocks diameter 4 mm to diameter 8 mm. (Delivery without padlocks) Switch position OI, front plate black. Four-hole mounting.