Further information for Schneider Electric V6 motor protection switch base unit
Complementary
Mounting Support
Symmetrical rail; Plate
Performance Level
High performance
Number of Poles
3P
Contact Type and Composition
3 NO
Network type
AC; DC
Network frequency
50/60 Hz
[Ue] IEC Rated Operational Voltage
690 V AC 50/60 Hz
IEC Rated Operational Power in W
30 kW at 230...240 V (AC-3); 37 kW at 400...415 V (AC-3); 37 kW at 690 V (AC-3); 45 kW at 500 V (AC-3); 45 kW at 690 V (AC-23A); 55 kW at 500 V (AC-23A); 30 kW at 230...240 V (AC-23A); 45 kW at 400...415 V (AC-23A)
[Ie] Rated Operational Current
83 A AC-23 Ue: 400 V
[Ith] Conventional Free Air Thermal Current
175 A
[Ithe] Conventional Enclosed Thermal Current
140 A
Making capacity ( I Rms)
1750 A at 400 V AC-22A; 1750 A at 400 V AC-23A; 1600 A at 400 V AC-21A
Breaking Capacity
1400 A at 400 V (AC-21A); 1400 A at 400 V (AC-22A); 1400 A at 400 V (AC-23A)
Rated Conditional Short Circuit Current
10 kA at 400 V - associated fuse 200 A aM; 10 kA at 400 V - associated fuse 200 A gG
[Icm] Rated Short Circuit Making Capacity
2.8 kA at 400 V at Ipeak
Intermittent duty class
30
[Uimp] rated impulse withstand voltage
8 kV
[Icw] rated short-time withstand Rms current
2100 A at 400 V duration: 1 s
Mechanical Durability
30000 cycles
Electrical Durability
30000 cycles AC-21; 30000 cycles DC-1...5
IEC Terminal Connection
Power circuit: screw clamp terminals70 mm² - flexible - with cable end; Power circuit: screw clamp terminals95 mm² - solid
Tightening Torque
Power circuit: 22.6 N.m - on screw clamp terminals
Height
125 mm
Width
90 mm
Depth
90 mm
Product Weight
0.9 kg
Suitability for isolation
Contractual warranty
Warranty (in months)
18
Environment
Standards
IEC 60947-3
Product Certifications
UL; CSA; GL; UKCA
Degree of Protection
IP20 conforming to IEC 60529
Protective Treatment
TC
Mechanical Robustness
Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6; Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Ambient Air Temperature for Operation
-20…50 °C
Fire Resistance
960 °C conforming to IEC 60695-2-1
Logistical informations
Country of origin
CZ
Main
Range
TeSys
Product Name
TeSys VARIO
Device Short Name
V
Product Type
Switch body
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
11.3 cm
Package 1 Width
13.2 cm
Package 1 Length
10.0 cm
Package 1 Weight
906.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
6
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
5.754 kg
V6 is a 3-pole switch body for TeSys Vario load break switches. With a rated voltage of 175A 690V, it is used in motor applications 45kW@400V AC-23. It requires an operating handle and an extension shaft to form a main or emergency stop switch. Additional modules (main pole, neutral, earthing module, auxiliary contacts) can complete the assembly. It is certified according to several standards (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach).