| Complementary |
| [Us] rated supply voltage | 24 V DC supplied by the bus coupler |
| Current consumption | 2 mA |
| Power dissipation in W | 0.5 W maximum |
| Standards | IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201 |
| Product certifications | CSA; UL; EAC (pending) |
| Mounting mode | Horizontal and vertical (35 mm symmetrical rail) |
| Connections - terminals | Measuring input: removable spring terminal block 3 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) rigid; Measuring input: removable spring terminal block 3 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Measuring input: removable spring terminal block 3 cable(s) 0.25…2.5 mm² (22 AWG...14 AWG) flexible with cable end |
| Width | 25 mm |
| Height | 118 mm |
| Depth | 114 mm |
| Net weight | 0.159 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for storage | -25…70 °C |
| Ambient air temperature for operation | -10…60 °C |
| Relative humidity | 5…95 % |
| Operating altitude | 0...2000 m without derating |
| IP degree of protection | IP20 |
| Pollution degree | 2 |
| Protective treatment | TC |
| Fire resistance | 960 °C conforming to UL 94 |
| Shock resistance | 15 gn (duration = 11 ms) conforming to IEC 60068-2-27 |
| Vibration resistance | 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic compatibility | Electrostatic discharge, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Line voltage circuit: fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4; Line voltage circuit: surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Product name | TeSys island |
| Device short name | TPRVM |
| Product or component type | Voltage interface module |
| Device presentation | Monitoring of the mains voltage powering the island; Reporting of the voltage to the bus coupler to enable power & energy monitoring |
| Function of module | Monitoring of voltages in single phase systems L-N or L-L; Monitoring of voltages in 3-phase systems without neutral N connection; Calculation of RMS phase voltages, voltage phase sequence, fundamental frequency; Identification of dip and swell events level and duration |
| Product compatibility | TPRBC bus coupler |
| [Ue] rated operational voltage | 690 V AC 47...63 Hz |
| [Ui] rated insulation voltage | 690 V conforming to IEC 61010-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 61010-1 |
| Overvoltage category | III |
| Monitoring type | Phase voltage 100...690 V; Phase frequency 47...63 Hz; Phase sequence |
| Measurement accuracy | Voltage: +/- 5 %, ; Frequency: +/- 1 Hz |
| Local signalling | 1 LED (green/red) for DS (device status); 1 LED (green/red) for VS (voltage status) |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 13.500 cm |
| Package 1 Length | 15.500 cm |
| Package 1 Weight | 235.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.295 kg |
TeSys island - load management system up to 80A. Interface card - voltage measurement. Connection screw terminals, status LED. Device width 22.5 mm, for DIN rail mounting. Interface for connecting the mains voltage and energy measurement at load level. Optimized for single-phase to three-phase loads, no control wiring required. Rated voltage 400 V, according to AC-3. TeSys island - Industry 4.0 optimized load management system with IIOT protocols. For measuring energy at load level.