Schneider Electric TPRPM038, EAN: 3606489832858

Schneider Electric TPRPM038 direct starter 38 A

Industrial Material > Automation > Industrial bus systems

Schneider Electric TPRPM038 direct starter 38 A

Lieske Part No. 1780051
Mfg Part No TPRPM038
EAN-Code 3606489832858
Manufacturer Schneider Electric
Here only 120,92 EUR
143,89 EUR incl. VAT

Further information for Schneider Electric TPRPM038 direct starter 38 A

Complementary
Protection typeThermal overload protection; Motor overheat; Overcurrent; Undercurrent; Jam; Long start; Stall; Rapid cycle lockout; Phase loss; Rapid restart lockout; Phase reversal; Phase sequence; Phase unbalance; Ground current
Monitoring typeTime device ON; Number of faults; Number of device power cycles; Average current Iavg; Average voltage Vavg; Max current Imax; Max voltage Vmax
Local signalling1 LED (green/red) for DS (device status); 1 LED (green/red) for LS (load status)
StandardsEN/IEC 60947-1; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1
Product certificationsEAC; CCC; CSA; UL
Mounting modeHorizontal and vertical (35 mm symmetrical DIN rail)
Connections - terminalsScrew-clamp terminals 1 cable(s) 1.5…10 mm² (16 AWG...8 AWG) rigid; Screw-clamp terminals 2 cable(s) 1.5…10 mm² (16 AWG...8 AWG) rigid; Screw-clamp terminals 1 cable(s) 2.5…10 mm² (14 AWG...8 AWG) flexible without cable end; Screw-clamp terminals 2 cable(s) 2.5…10 mm² (14 AWG...8 AWG) flexible without cable end; Screw-clamp terminals 1 cable(s) 1.5…10 mm² (16 AWG...10 AWG) flexible with cable end; Screw-clamp terminals 2 cable(s) 1.5…6 mm² (16 AWG...10 AWG) flexible with cable end
Tightening torque2.5 N.m - with screwdriver flat Ø 6 mm; 2.5 N.m - with screwdriver Philips No 3
Width45 mm
Height121 mm
Depth115 mm
Net weight0.255 kg
Contractual warranty
Warranty (in months)18
Environment
Ambient air temperature for storage-25…70 °C
Ambient air temperature for operation-10…50 °C without derating; 50…60 °C with current derating
Relative humidity5…95 %
Operating altitude0...2000 m without derating
IP degree of protectionIP20
Pollution degree2
Protective treatmentTC
Fire resistance960 °C conforming to UL 94; 850 °C conforming to IEC 60695-2-1; 650 °C conforming to IEC 60695-2-12
Shock resistance15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration resistance1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Logistical informations
Country of originFR
Main
Range of productTeSys
Product nameTeSys island
Device short nameTPRPM
Product or component typePower module
Device presentationPower module connected to an automation controller through a bus coupler; Operational only when connected to a bus coupler
Function availableUpstream voltage presence detection; Electronic thermal overload protection; Monitoring of currents; Control of third party power devices when associated to TPRDG IO module
Product compatibilityTPRBC bus coupler; TPRDG digital IO module; TPRAN analog IO module
Poles description3P
Motor power kW9 kW at 230 V AC 50 Hz; 18.5 kW at 380...415 V AC 50 Hz; 18.5 kW at 440 V AC 50 Hz; 18.5 kW at 500 V AC 50 Hz; 18.5 kW at 690 V AC 50 Hz
motor power HP (UL / CSA)2 hp at 120 V AC 60 Hz for 1 phase motors; 5 hp at 240 V AC 60 Hz for 1 phase motors; 10 hp at 208 V AC 60 Hz for 3 phases motors; 10 hp at 240 V AC 60 Hz for 3 phases motors; 20 hp at 480 V AC 60 Hz for 3 phases motors; 25 hp at 600 V AC 60 Hz for 3 phases motors
[Ie] rated operational current38 A (at
[Ith] conventional free air thermal current40 A (at 50 °C)
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV
Overvoltage categoryIII
Thermal protection adjustment range0.76…38 A
Thermal overload classClass 5…30
ResetRemotely or automatically
[Uc] control circuit voltage24 V DC supplied by the bus coupler
Current consumption60 mA
Power dissipation in W0.9 W at Ie AC-3
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height5.0 cm
Package 1 Width12.5 cm
Package 1 Length13.0 cm
Package 1 Weight308.0 g
Unit Type of Package 2S02
Number of Units in Package 214
Package 2 Height15.0 cm
Package 2 Width30.0 cm
Package 2 Length40.0 cm
Package 2 Weight4.657 kg
TeSys island - load management system up to 80A. Direct starter, 38 A, 18.5 kW for overload protection and management without switching function. Connection screw terminals, status LED. Device width 45 mm, for DIN rail mounting. 3-pole load output. Optimized for single-phase to three-phase loads, no control wiring required. Rated voltage 400 V, according to AC-3. TeSys island - Industry 4.0 optimized load management system with IIOT protocols. Load output card for measuring relevant values. Functions overload protection, monitoring. For connecting e.g. soft starters, semiconductor relays and for monitoring load output groups.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1780051
qrcode für Schneider Electric TPRPM038 direct starter 38 A