| Complementary |
| Protection type | Thermal overload protection; Motor overheat; Overcurrent; Undercurrent; Jam; Long start; Stall; Rapid cycle lockout; Phase loss; Rapid restart lockout; Phase reversal; Phase unbalance; Phase sequence; Ground current |
| Monitoring type | Time device ON; Number of faults; Number of device power cycles; Average current Iavg; Average voltage Vavg; Max current Imax; Max voltage Vmax |
| Local signalling | 1 LED (green/red) for DS (device status); 1 LED (green/red) for LS (load status) |
| Standards | EN/IEC 60947-1; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product certifications | CCC; CSA; EAC; UL |
| Mounting mode | Horizontal and vertical (35 mm symmetrical DIN rail) |
| Connections - terminals | Screw-clamp terminals 1 cable(s) 1…4 mm² (16 AWG...12 AWG) rigid; Screw-clamp terminals 2 cable(s) 1…4 mm² (16 AWG...12 AWG) rigid; Screw-clamp terminals 1 cable(s) 1.5…4 mm² (16 AWG...12 AWG) flexible without cable end; Screw-clamp terminals 2 cable(s) 1.5…4 mm² (16 AWG...12 AWG) flexible without cable end; Screw-clamp terminals 1 cable(s) 1…4 mm² (16 AWG...12 AWG) flexible with cable end; Screw-clamp terminals 2 cable(s) 1…2.5 mm² (16 AWG...14 AWG) flexible with cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2 |
| Width | 45 mm |
| Height | 121 mm |
| Depth | 115 mm |
| Net weight | 0.255 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for storage | -25…70 °C |
| Ambient air temperature for operation | -10…50 °C without derating; 50…60 °C with current derating |
| Relative humidity | 5…95 % |
| Operating altitude | 0...2000 m without derating |
| IP degree of protection | IP20 |
| Pollution degree | 2 |
| Protective treatment | TC |
| Fire resistance | 960 °C conforming to UL 94; 850 °C conforming to IEC 60695-2-1; 650 °C conforming to IEC 60695-2-12 |
| Shock resistance | 15 gn (duration = 11 ms) conforming to IEC 60068-2-27 |
| Vibration resistance | 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys |
| Product name | TeSys island |
| Device short name | TPRPM |
| Product or component type | Power module |
| Device presentation | Power module connected to an automation controller through a bus coupler; Operational only when connected to a bus coupler |
| Function available | Upstream voltage presence detection; Electronic thermal overload protection; Monitoring of currents; Control of third party power devices when associated to TPRDG IO module |
| Product compatibility | TPRBC bus coupler; TPRDG digital IO module; TPRAN analog IO module |
| Poles description | 3P |
| Motor power kW | 2.2 kW at 230 V AC 50 Hz; 4 kW at 380...415 V AC 50 Hz; 4 kW at 440 V AC 50 Hz; 5.5 kW at 500 V AC 50 Hz; 5.5 kW at 690 V AC 50 Hz |
| motor power HP (UL / CSA) | 0.33 hp at 120 V AC 60 Hz for 1 phase motors; 1 hp at 240 V AC 60 Hz for 1 phase motors; 2 hp at 208 V AC 60 Hz for 3 phases motors; 2 hp at 240 V AC 60 Hz for 3 phases motors; 5 hp at 480 V AC 60 Hz for 3 phases motors; 7.5 hp at 600 V AC 60 Hz for 3 phases motors |
| [Ie] rated operational current | 9 A (at |
| [Ith] conventional free air thermal current | 15 A (at 50 °C) |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Overvoltage category | III |
| Thermal protection adjustment range | 0.18…9 A |
| Thermal overload class | Class 5…30 |
| Reset | Remotely or automatically |
| [Uc] control circuit voltage | 24 V DC supplied by the bus coupler |
| Current consumption | 60 mA |
| Power dissipation in W | 0.6 W at Ie AC-3 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 12.500 cm |
| Package 1 Length | 13.000 cm |
| Package 1 Weight | 304.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 14 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.541 kg |
TeSys island - load management system up to 80A. Direct starter, 9 A, 4 kW for overload protection and management without switching function. Connection screw terminals, status LED. Device width 45 mm, for DIN rail mounting. 3-pole load output. Optimized for single-phase to three-phase loads, no control wiring required. Rated voltage 400 V, according to AC-3. TeSys island - Industry 4.0 optimized load management system with IIOT protocols. Load output card for measuring relevant values. Functions overload protection, monitoring. For connecting e.g. soft starters, semiconductor relays and for monitoring load output groups.