| Complementary |
| [Us] rated supply voltage | 24 V DC supplied by the bus coupler |
| Current consumption | 160 mA |
| Power dissipation in W | 0.5 W maximum |
| [Uimp] rated impulse withstand voltage | 0.5 kV conforming to IEC 61010-1 |
| Standards | IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201 |
| Product certifications | CSA; UL; EAC (pending) |
| Mounting mode | Horizontal and vertical (35 mm symmetrical rail) |
| Connections - terminals | Input/output circuit: removable spring terminal block 8 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) rigid; Input/output circuit: removable spring terminal block 8 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Input/output circuit: removable spring terminal block 8 cable(s) 0.25…2.5 mm² (22 AWG...14 AWG) flexible with cable end |
| Width | 25 mm |
| Height | 118 mm |
| Depth | 114 mm |
| Net weight | 0.172 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Ambient air temperature for storage | -25…70 °C |
| Ambient air temperature for operation | -10…60 °C |
| Relative humidity | 5…95 % |
| Operating altitude | 0...2000 m without derating |
| IP degree of protection | IP20 |
| Pollution degree | 2 |
| Protective treatment | TC |
| Fire resistance | 960 °C conforming to UL 94 |
| Shock resistance | 15 gn (duration = 11 ms) conforming to IEC 60068-2-27 |
| Vibration resistance | 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic compatibility | Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4; Surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys |
| Product name | TeSys island |
| Device short name | TPRAN |
| Product or component type | Analog IO module |
| Device presentation | IO module providing 2 analog inputs and 1 analog output; Enabling advanced control functions in a TeSys island system; Operational only when connected to a bus coupler TPRBC |
| Function of module | Measurement of voltage, current or temperature on 2 configurable analog inputs; Driving voltage or current source on 1 configurable analog output |
| Product compatibility | TPRBC bus coupler |
| Analogue input number | 2 isolated with common point |
| Measurement accuracy | +/- 0.1 % of full scale voltage 25 °C; +/- 0.1 % of full scale current 25 °C; +/- 0.1 % of full scale temperature probe 25 °C; +/- 0.1 % of full scale in positive temperature range thermocouple 25 °C; +/- 0.4 % of full scale in negative temperature range thermocouple 25 °C |
| Analogue input resolution | 15 bits + sign full scale |
| Input impedance | = 1 MOhm voltage; >= 1 MOhm thermocouple; >= 1 MOhm temperature probe |
| Analogue output number | 1 isolated |
| Analogue output type | Current 4...20 mA; Current 0...20 mA; Voltage 0...10 V; Voltage - 10...10 V |
| Analogue output resolution | 12 bits, 4...20 mA full scale; 12 bits, 0...20 mA full scale; 12 bits, 0...10 V full scale; 11 bits + sign, - 10...10 V full scale |
| Type of cable | Twisted shielded pairs cable |
| Local signalling | 1 LED (green/red) for DS (device status) |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 13.500 cm |
| Package 1 Length | 15.500 cm |
| Package 1 Weight | 245.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.654 kg |
TeSys island - load management system up to 80A. Analog input and output card. Push-in connection, control voltage 24V DC, status LED, 2 analog inputs and 1 output. Device width 22.5 mm, for DIN rail mounting. Analog input and output card for collecting and transmitting application-specific signals. Analog inputs Monitoring of RTD, thermocouple, voltage and current measurements (thermocouple, PT100, PT1000, NI100, NI1000, NI1000, 0-10 V, -10-10V, 0-20 mA, 4-20 mA). Analog outputs Voltage and current output via 1 configurable analog output (0-10 V, -10-10 V, 0-20 mA, 4-20 mA). TeSys island - Industry 4.0 optimized load management system with IIOT protocols.