| Complementary |
| Current consumption | 5 mA at 5 V DC via bus connector at state on; 35 mA at 5 V DC via bus connector at state off; 0 mA at 24 V DC via bus connector at state on; 10 mA at 24 V DC via bus connector at state off; 1200 mA at 24 V DC external power supply at state on |
| Input voltage limits | 19.2...28.8 V per input |
| Input current limits | 5 mA per input |
| Response time | < 10 ms turn-on for input; < 10 ms turn-off for input |
| Output voltage | 24 V DC for transistor output |
| Maximum load current | 800 mA per channel in starting mode during 100 ms; 300 mA per channel in normal mode |
| Insulation | Between the RJ45 connectors and internal logic at 500 V AC; Non-insulated between RJ45 connectors |
| Output protection type | Against overload, protection technology: current limiter |
| Reset | Automatic reset |
| Local signalling | 3 LEDs green for input status per channel; 2 LEDs green for output status per channel |
| Electrical connection | 3 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for connecting the 24 V DC power supply; 4 RJ45 connectors for connecting the motor starters |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Depth | 85 mm |
| Width | 30 mm |
| Net weight | 0.115 kg |
| DC supply voltage | 24 V |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Product certifications | CE; cULus; UKCA; RCM; EAC |
| Marking | CE |
| Resistance to electrostatic discharge | 8 kV in air conforming to EN/IEC 61000-4-2; 4 kV on contact conforming to EN/IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
| Resistance to fast transients | 1 kV for input conforming to EN/IEC 61000-4-4; 1 kV for output conforming to EN/IEC 61000-4-4 |
| Surge withstand | 1 kV input common mode conforming to EN/IEC 61000-4-5; 1 kV output common mode conforming to EN/IEC 61000-4-5 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6; 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission | Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011 |
| Ambient air temperature for operation | -10…35 °C vertical installation; -10…55 °C horizontal installation |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 with protective cover in place |
| Pollution degree | 2 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on DIN rail; 3 gn at 8.4…150 Hz on DIN rail; 3.5 mm at 5…8.4 Hz on panel; 3 gn at 8.4…150 Hz on panel |
| Shock resistance | 15 gn for 11 ms |
| Logistical informations |
| Country of origin | TW |
| Main |
| Range of product | Modicon TM3 |
| Product or component type | Parallel interface module |
| Product specific application | TeSys U |
| [Us] rated supply voltage | 24 V DC by external supply (- 15...20 %) |
| Number of input channels | 12 |
| Number of output channels | 8 |
| Range compatibility | Modicon M221; Modicon M251; Modicon M241; Modicon M262 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.500 cm |
| Package 1 Width | 12.500 cm |
| Package 1 Length | 10.500 cm |
| Package 1 Weight | 215.000 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 42 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 10.000 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 504 |
| Package 3 Height | 80.000 cm |
| Package 3 Width | 105.000 cm |
| Package 3 Length | 125.000 cm |
| Package 3 Weight | 62.296 kg |
TeSys motor starter module Modicon TM3. For expanding Modicon M221, M241, M251 and M262 PLC controllers with I/O channels. Compatible with third-party controllers using Modicon TM3 bus coupler. Enables connection of up to 4 TeSys motor starters via RJ45 connections and quick connection system. The power supply is via 24VDC. Planning and configuration using EcoStruxure Machine Expert software or standalone configurator (download from www.se.com). Ambient temperature during operation -10°C to +55°C. Mounting on 35mm DIN rail or directly on control panel with optional holder. Certifications according to CE, UL, CSA.