Complementary
Safety reliability dataDC = 95 % conforming to ISO 13849-1; PFHd = 5E-9 1/h conforming to IEC 61508-1 1 operation/hour DC-13 24 V DC
Synchronisation time between inputsUnlimited
Output typeRelay instantaneous opening, 3 NO circuit(s), potential free
Number of safety circuits3 NO for relay instantaneous opening
Maximum switching voltage230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening); 24 V utilisation category DC-13 (relay instantaneous opening)
[Us] rated supply voltage24 V - 15...20 % DC
Power consumption in W0.2 W at 5 V DC; 3.6 W at 24 V DC
Input protection typeInternal, electronic
[Uc] control circuit voltage24 V DC
Maximum cable distance between devices30 m
Breaking capacity360 VA holding AC-15 B300 relay output; 3600 VA inrush AC-15 B300 relay output
Output thermal current6 A per relay for relay output
[Ith] conventional free air thermal current18 A
Associated fuse rating4 A gG or gL for relay output conforming to IEC 60947-5-1; 6 A fast blow for relay output conforming to IEC 60947-5-1
Minimum output current10 mA for relay output
Output voltage10 V relay output
Maximum response time on input open40 ms
[Ui] rated insulation voltage300 V (pollution degree 2) conforming to IEC 60647-5-1
[Uimp] rated impulse withstand voltage4 kV overvoltage category III conforming to IEC 60647-5-1
Current consumption100 mA at 24 V DC external supply
Local signalling8 LEDs (green/red) for user
Electrical connectionScrew terminal
Product compatibilitySafety light curtains conforming to EN/IEC 61496-1 (type 4)
StandardsISO 13849-1:2008; ISO 13849-2:2012; IEC 62061:2005; IEC 61508:2010; IEC 60947-5-1:2010; IEC 61131-2:2007; IEC 60204-1:2005; IEC 60204-1:2009/A1; IEC 61010-1:2010; EN 50581:2012
Product certificationsTÜV; RCM; ANSI Haz Loc Class 1 Division 2 (pending); CSA Haz Loc Class 1 Division 2 (pending); EAC; CSA 61010-2-201 (pending); UL 61010-2-201
MarkingCE; EFUP 10; UL; CSA; EAC; RCM; TÜV
Mounting supportTop hat type TH35-7.5 rail conforming to IEC 60715; Top hat type TH35-15 rail conforming to IEC 60715; wall mount using attached fasteners
Height94 mm
Depth73 mm
Width43.7 mm
Net weight0.19 kg
Contractual warranty
Warranty (in months)18
Environment
Resistance to electrostatic discharge8 kV in air conforming to IEC 61000-4-2; 6 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients3 kV for power lines (DC) (DC) conforming to IEC 61000-4-4; 2 kV for I/O lines conforming to IEC 61000-4-4
Surge withstand1 kV power lines (DC) differential mode conforming to IEC 61000-4-5 DC; 1 kV power lines (DC) common mode conforming to IEC 61000-4-5 DC
Resistance to conducted disturbances10 V 0.15...80 MHz conforming to IEC 61000-4-6
Electromagnetic emissionRadiated emissions - test level: 50 dBµV/m class A ( 24 V DC) at 30…230 Hz conforming to IEC 61131-3; Radiated emissions - test level: 57 dBµV/m class A ( 24 V DC) at 230…1000 Hz conforming to IEC 61131-3
Ambient air temperature for operation-10…55 °C horizontal installation
Ambient air temperature for storage-25…70 °C
Relative humidity10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP degree of protectionIP20 (terminals) conforming to IEC 60529
Pollution degree2
Operating altitude0...2000 m
Storage altitude0…3000 m
Vibration resistance+/- 3.5 mm (f= 5…150 Hz) conforming to IEC 60068-2-6
Shock resistance15 gn for 11 ms conforming to IEC 60068-2-27
Mechanical robustnessBumps 6 ms 300 shocks (25 gn) conforming to IEC 60068-2-27
Logistical informations
Country of originFR
Main
Range of productModicon TM3 Safety
Product or component typeSafety module
Device short nameTM3SAFL
Safety module applicationFor emergency stop, switch and safety light curtain monitoring
Function of moduleEmergency stop monitoring 2-channel wiring; Monitoring of a movable guard with 2 switches and automatic start; Monitoring of a movable guard; Multiple emergency stop monitoring 2-channel wiring; Proximity sensor monitoring PNP/PNP; Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP
Safety levelCan reach PL d/category 3 conforming to ISO 13849-1: 2008; Can reach PL d/category 3 conforming to ISO 13849-2: 2012; Can reach SILCL 2 conforming to IEC 62061: 2005; Can reach SIL 2 conforming to IEC 61508: 2010
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height7.500 cm
Package 1 Width10.600 cm
Package 1 Length12.500 cm
Package 1 Weight285.000 g
Unit Type of Package 2S03
Number of Units in Package 218
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight5.434 kg
Modicon TM3 safety module. For expanding Modicon M221, M241, M251 and M262 PLC controllers with functional safety modules. Compatible with third-party controllers using Modicon TM3 bus couplers. 2 digital safety inputs (24VDC, 100mA), 3 parallel digital safety outputs. For connecting emergency stops (EN/IEC 60204-1, EN/ISO 13850) and switches in protective devices (EN/ISO 14119) as well as safety light curtains and safety sensors with PNP/NPN outputs. Maximum achievable safety level PLd / Category 3 according to EN/ISO 13849-1, SIL CL2 according to EN/IEC 62061. Safety-relevant functions are managed exclusively by the safety module, independently of the rest of the system. Relay states can be read directly via the TM3 backplane bus. The digital outputs are designed as Realis (24VDC / 230VAC, 6A). Planning and configuration using EcoStruxure Machine Expert software or standalone configurator (download from www.se.com). Connection via removable screw terminal blocks. Ambient temperature during operation -10°C to +55°C. Installation on 35mm DIN rail or directly on control panel with optional holder. Certifications according to CE, UL, CSA, RCM, EAC, CCC.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1850831
qrcode für Schneider Electric TM3SAFL5R screw terminal E-STOP/SLB CAT.4