| Complementary |
| Safety reliability data | DC = 95 % conforming to ISO 13849-1; SFF = 95 % conforming to IEC 61508-1; HFT = 1 conforming to IEC 61508-1; Type = A conforming to IEC 61508-1; PFHd = 5E-9 1/h conforming to IEC 61508-1; PFHd = 30E-9 1/h conforming to IEC 61508-1; MTTFd = 500 years conforming to ISO 13849-1; MTTFd = 85 years conforming to ISO 13849-1 |
| Synchronisation time between inputs | Unlimited |
| Output type | Relay instantaneous opening, 3 NO circuit(s), potential free |
| Number of safety circuits | 3 NO for relay instantaneous opening |
| Maximum switching voltage | 230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening); 24 V utilisation category DC-13 (relay instantaneous opening) |
| [Us] rated supply voltage | 24 V - 15...20 % DC |
| Power consumption in W | 0.2 W at 5 V DC; 3.6 W at 24 V DC |
| Input protection type | Internal, electronic |
| [Uc] control circuit voltage | 24 V DC |
| Maximum cable distance between devices | 30 m |
| Breaking capacity | 360 VA holding AC-15 B300 relay output; 3600 VA inrush AC-15 B300 relay output |
| Output thermal current | 6 A per relay for relay output |
| [Ith] conventional free air thermal current | 18 A |
| Associated fuse rating | 4 A gG or gL for relay output conforming to IEC 60947-5-1; 6 A fast blow for relay output conforming to IEC 60947-5-1 |
| Minimum output current | 10 mA for relay output |
| Output voltage | 10 V relay output |
| Maximum response time on input open | 40 ms |
| [Ui] rated insulation voltage | 300 V (pollution degree 2) conforming to IEC 60647-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV overvoltage category III conforming to IEC 60647-5-1 |
| Current consumption | 100 mA at 24 V DC external supply |
| Local signalling | 6 LEDs (green/red) for user |
| Electrical connection | Spring terminal |
| Standards | ISO 13849-1:2008; ISO 13849-2:2012; IEC 62061:2005; IEC 61508:2010; IEC 60947-5-1:2010; IEC 61131-2:2007; IEC 60204-1:2005; IEC 60204-1:2009/A1; IEC 61010-1:2010; EN 50581:2012 |
| Product certifications | UL 61010-2-201; CSA 61010-2-201 (pending); TÜV; EAC; CSA Haz Loc Class 1 Division 2 (pending); ANSI Haz Loc Class 1 Division 2 (pending); RCM |
| Marking | CSA; EAC; CE; RCM; UL; TÜV; EFUP 10 |
| Mounting support | Top hat type TH35-7.5 rail conforming to IEC 60715; Top hat type TH35-15 rail conforming to IEC 60715; wall mount using attached fasteners |
| Height | 94 mm |
| Depth | 73 mm |
| Width | 43.7 mm |
| Net weight | 0.19 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2; 6 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to IEC 61000-4-8 |
| Resistance to fast transients | 3 kV for power lines (DC) (DC) conforming to IEC 61000-4-4; 2 kV for I/O lines conforming to IEC 61000-4-4 |
| Surge withstand | 1 kV power lines (DC) differential mode conforming to IEC 61000-4-5 DC; 1 kV power lines (DC) common mode conforming to IEC 61000-4-5 DC |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to IEC 61000-4-6 |
| Electromagnetic emission | Radiated emissions - test level: 50 dBµV/m class A ( 24 V DC) at 30…230 Hz conforming to IEC 61131-3; Radiated emissions - test level: 57 dBµV/m class A ( 24 V DC) at 230…1000 Hz conforming to IEC 61131-3 |
| Ambient air temperature for operation | -10…55 °C horizontal installation |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529 |
| Pollution degree | 2 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | +/- 3.5 mm (f= 5…150 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Mechanical robustness | Bumps 6 ms 300 shocks (25 gn) conforming to IEC 60068-2-27 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | Modicon TM3 Safety |
| Product or component type | Safety module |
| Device short name | TM3SAC |
| Safety module application | For emergency stop and switch monitoring |
| Function of module | Emergency stop monitoring 1-channel wiring; Emergency stop monitoring 2-channel wiring; Monitoring of a movable guard with 2 switches and automatic start |
| Safety level | Can reach PL d/category 3 conforming to ISO 13849-1: 2008; Can reach PL d/category 3 conforming to ISO 13849-2: 2012; Can reach SILCL 2 conforming to IEC 62061: 2005; Can reach SIL 2 conforming to IEC 61508: 2010 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.500 cm |
| Package 1 Width | 10.600 cm |
| Package 1 Length | 12.500 cm |
| Package 1 Weight | 269.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 18 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.337 kg |
Modicon TM3 safety module. For expanding Modicon M221, M241, M251 and M262 PLC controllers with functional safety modules. Compatible with third-party controllers using Modicon TM3 bus couplers. 1 or 2 digital safety inputs depending on the connection (24VDC, 100mA), 3 parallel digital safety outputs. For connecting emergency stops (EN/IEC 60204-1, EN/ISO 13850) and switches in protective devices (EN/ISO 14119). Maximum achievable safety level PLd / Category 3 according to EN/ISO 13849-1, SIL CL2 according to EN/IEC 62061. Safety-relevant functions are managed exclusively by the safety module, independently of the rest of the system. Relay states can be read directly via the TM3 backplane bus. The digital outputs are designed as Realis (24VDC / 230VAC, 6A). Planning and configuration using EcoStruxure Machine Expert software or standalone configurator (download from www.se.com). Connection via removable spring-loaded terminal blocks. Ambient temperature during operation -10°C to +55°C. Installation on 35mm DIN rail or directly on control panel with optional holder. Certifications according to CE, UL, CSA, RCM, EAC, CCC.