| Complementary |
| Discrete I/O number | 16 |
| Maximum number of I/O expansion module | 7 (local I/O-Architecture); 14 (remote I/O-Architecture) |
| Supply voltage limits | 20.4…28.8 V |
| Inrush current | 35 A |
| Maximum power consumption in W | 22.5 W at 24 V (with max number of I/O expansion module); 3.6 W at 24 V (without I/O expansion module) |
| Power supply output current | 0.52 A 5 V for expansion bus; 0.46 A 24 V for expansion bus |
| Discrete input logic | Sink or source (positive/negative) |
| Discrete input voltage | 24 V |
| Discrete input voltage type | DC |
| Analogue input resolution | 10 bits |
| LSB value | 10 mV |
| Conversion time | 1 ms per channel + 1 controller cycle time for analogue input analog input |
| Permitted overload on inputs | +/- 30 V DC for 5 min (maximum) for analog input; +/- 13 V DC (permanent) for analog input |
| Voltage state 1 guaranteed | >= 15 V for input |
| Discrete input current | 7 mA for discrete input; 5 mA for fast input |
| Input impedance | 100 kOhm for analog input; 3.4 kOhm for input; 4.9 kOhm for fast input |
| Response time | 35 µs turn-off, I2...I5 terminal(s) for input; 10 ms turn-on for output; 10 ms turn-off for output; 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input; 35 µs turn-on, other terminals terminal(s) for input; 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input; 100 µs turn-off, other terminals terminal(s) for input |
| Configurable filtering time | 0 ms for input; 3 ms for input; 12 ms for input |
| Output voltage limits | 125 V DC; 277 V AC |
| Maximum current per output common | 7 A |
| Absolute accuracy error | +/- 1 % of full scale for analog input |
| Switching frequency | 20 switching operations/minute with maximum load |
| Mechanical durability | 20000000 cycles for relay output |
| Minimum load | 1 mA at 5 V DC for relay output |
| Protection type | Without protection at 5 A |
| Reset time | 1 s |
| Memory capacity | 256 kB for user application and data RAM with 10000 instructions; 256 kB for internal variables RAM |
| Data backed up | 256 kB built-in flash memory for backup of application and data |
| Data storage equipment | 2 GB SD card (optional) |
| Battery type | BR2032 or CR2032X lithium non-rechargeable |
| Backup time | 1 year at 25 °C (by interruption of power supply) |
| Execution time for 1 KInstruction | 0.3 ms for event and periodic task; 0.7 ms for other instruction |
| Execution time per instruction | 0.2 µs Boolean |
| Exct time for event task | 60 µs response time |
| Application structure | 1 configurable freewheeling/cyclic master task; 1 cyclic auxiliary task; 8 interrupt tasks |
| Maximum size of object areas | 255 %TM timers; 8000 %MW memory words; 255 %C counters; 512 %M memory bits; 512 %KW constant words |
| Realtime clock | With |
| Regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
| Counting input number | 4 fast input (HSC mode) at 100 kHz 32 bits |
| counter function | Pulse/direction; A/B; Single phase |
| Integrated connection type | USB port with mini B USB 2.0 connector; Non isolated serial link serial 1 with RJ45 connector and RS485 interface ; Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface |
| Supply | (serial 1)serial link supply: 5 V |
| Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for USB |
| Communication port protocol | USB port: USB - SoMachine-Network; Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network |
| Communication service | Modbus slave; Modbus master |
| Local signalling | 1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED (green) for SL1; 1 LED (green) for SL2; 1 LED per channel (green) for I/O state |
| Electrical connection | terminal block, 3 terminal(s) for connecting the 24 V DC power supply; connector, 4 terminal(s) for analogue inputs; Mini B USB 2.0 connector for a programming terminal; removable screw terminal block, 10 terminal(s) for inputs; removable screw terminal block, 11 terminal(s) for outputs |
| Maximum cable distance between devices | Shielded cable: |
| Insulation | Between input and internal logic at 500 V AC; Between fast input and internal logic at 500 V AC; Non-insulated between inputs; Between output and internal logic at 500 V AC; Between output groups at 500 V AC; Non-insulated between analogue input and internal logic; Non-insulated between analogue inputs |
| Marking | CE |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Depth | 70 mm |
| Width | 70 mm |
| Net weight | 0.264 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 61131-2; UL 508; CAN/CSA C22.2 No. 213; IACS E10; ANSI/ISA 12-12-01 |
| Product certifications | DNV-GL; ABS; LR; cULus; RCM; EAC; CE; UKCA; cULus HazLoc |
| Environmental characteristic | Ordinary and hazardous location |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to IEC 61000-4-8 |
| Resistance to fast transients | 2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Immunity to microbreaks | 10 ms |
| Ambient air temperature for operation | -10…55 °C (horizontal installation); -10…35 °C (vertical installation) |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 with protective cover in place |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 1 gn at 8.4…150 Hz on symmetrical rail; 1 gn at 8.4…150 Hz on panel mounting |
| Shock resistance | 98 m/s² for 11 ms |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | Modicon M221 |
| Product or component type | Logic controller |
| [Us] rated supply voltage | 24 V DC |
| Discrete input number | 8, discrete input conforming to IEC 61131-2 Type 1 |
| Analogue input number | 2 at 0...10 V |
| Discrete output type | Relay normally open |
| Discrete output number | 8 relay |
| Discrete output voltage | 5...125 V DC; 5...250 V AC |
| Discrete output current | 2 A |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.000 cm |
| Package 1 Width | 10.000 cm |
| Package 1 Length | 13.000 cm |
| Package 1 Weight | 460.000 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 11.500 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 288 |
| Package 3 Height | 105.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 148.000 kg |
SPS-Steuerung Modicon M221 im Kompaktformat mit 0,2µs / boolsche Anweisung für die Automatisierung von einfachen industriellen Maschinen. Insgesamt 16 integrierte E/A, davon 8 digitale (4 Standard mit 5kHz und 4 HSC mit 100kHz) Eingänge, 8 digitale Ausgänge. Zusätzlich 2 analoge (0V bis 10V / 10Bit) Eingänge. Zwei RS485/RS232-Schnittstellen mit RJ45-Buchse für Modbus ASCII/RTU Master/Slave, ASCII character string, Modbus Serial IO Scanner. Die Spannungsversorgung erfolgt über 24VDC. Die digitalen Ausgänge sind als Relais (2A) ausgeführt. 640 kB integrierter RAM-Speicher und 2 MB Flash-Speicher. Integrierte Regelung für bis zu 2 koordinierte Achsen. Position Control (PTO) mit Trapez- oder S-Profil für 2 Achsen in Pulse-Direction (P/D)-Mode oder eine Achse in CW/CCW-Mode. Ausgestattet mit einem Steckplatz für SD-Karte, einem USB-mini-B-Port zur Programmierung, einem Run/Stop-Schalter und QR-Code für direkten Zugriff auf technische Dokumentation. Lokale und dezentrale E/A-Erweiterung mit Modicon TM3 E/A-System. Programmierung und Konfiguration mittels kostenfreier Software EcoStruxure Machine Expert - Basic (Download über www.se.com). SPS-Programmierung nach IEC 61131-3 in den Programmiersprachen Anweisungsliste (AWL), Kontaktplan (KOP) oder Ablaufsprache (Grafcet Liste/ SFC). Anschluss über abnehmbare Schraubklemmleiste. Umgebungstemperatur im Betrieb -15°C bis +50°C. Montage auf 35mm DIN-Hutschiene oder direkt auf Schalttafel. Zertifiziert nach CE, cULus Listing Mark, CSA, RCM, EAC, LR, ABS, DNV-GL, cCSAus Gefahrenzone.