Schneider Electric TM221C40U, EAN: 3606485408637

Schneider Electric TM221C40U PLC 2AE/24DE/16DA SINK screw terminal

Industrial Material > Automation > PLC Systems

Schneider Electric TM221C40U PLC 2AE/24DE/16DA SINK screw terminal

Lieske Part No. 1770830
Mfg Part No TM221C40U
EAN-Code 3606485408637
Manufacturer Schneider Electric
Here only 353,17 EUR
420,27 EUR incl. VAT

Further information for Schneider Electric TM221C40U PLC 2AE/24DE/16DA SINK screw terminal

Complementary
Discrete I/O number40
Maximum number of I/O expansion module7 (local I/O-Architecture); 14 (remote I/O-Architecture)
Supply voltage limits20.4…28.8 V
Inrush current35 A
Maximum power consumption in W4.1 W at 24 V (without I/O expansion module); 16 W at 24 V (with max number of I/O expansion module)
Power supply output current0.52 A 5 V for expansion bus; 0.3 A 24 V for expansion bus
Discrete input logicSink or source (positive/negative)
Discrete input voltage24 V
Discrete input voltage typeDC
Analogue input resolution10 bits
LSB value10 mV
Conversion time1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted overload on inputs+/- 30 V DC for 5 min (maximum) for analog input; +/- 13 V DC (permanent) for analog input
Voltage state 1 guaranteed>= 15 V for input
Discrete input current7 mA for discrete input; 5 mA for fast input
Input impedance3.4 kOhm for discrete input; 100 kOhm for analog input; 4.9 kOhm for fast input
Response time35 µs turn-off, I2...I5 terminal(s) for input; 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input; 35 µs turn-on, other terminals terminal(s) for input; 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input; 100 µs turn-off, other terminals terminal(s) for input; 300 µs turn-on, turn-off, other terminals terminal(s) for output; 5 µs turn-on, turn-off, Q0...Q3 terminal(s) for output
Configurable filtering time0 ms for input; 3 ms for input; 12 ms for input
Discrete output logicNegative logic (sink)
Maximum current per output common4 A
Output frequency0.1 kHz for output at Q4...Q15; 100 kHz for fast output (PWM/PLS mode) at Q0...Q3
Absolute accuracy error+/- 1 % of full scale for analog input
Maximum leakage current0.1 mA for transistor output
Mechanical durability20000000 cycles for transistor output
Protection typeWithout protection
Memory capacity256 kB for user application and data RAM with 10000 instructions; 256 kB for internal variables RAM
Data backed up256 kB built-in flash memory for backup of application and data
Data storage equipment2 GB SD card (optional)
Battery typeBR2032 or CR2032X lithium non-rechargeable
Backup time1 year at 25 °C (by interruption of power supply)
Execution time for 1 KInstruction0.3 ms for event and periodic task
Execution time per instruction0.2 µs Boolean
Exct time for event task60 µs response time
Maximum size of object areas8000 %MW memory words; 512 %KW constant words; 512 %M memory bits; 255 %C counters; 255 %TM timers
Realtime clockWith
Regulation loopAdjustable PID regulator up to 14 simultaneous loops
Positioning functionsPosition PTO 4 axe(s)pulse/direction mode (100 kHz); Position PTO 2 axe(s)CW/CCW mode (100 kHz)
Function availablePLS; PWM; Frequency generator
Counting input number4 fast input (HSC mode) at 100 kHz 32 bits
counter functionPulse/direction; Single phase; A/B
Integrated connection typeUSB port with mini B USB 2.0 connector; Non isolated serial link serial 1 with RJ45 connector and RS485 interface ; Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
Supply(serial)serial link supply: 5 V
Transmission rate1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for USB
Communication port protocolUSB port: USB - SoMachine-Network; Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Local signalling1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED (green) for SL1; 1 LED (green) for SL2; 1 LED per channel (green) for I/O state
Electrical connectionremovable screw terminal block for inputs; removable screw terminal block for outputs; terminal block, 3 terminal(s) for connecting the 24 V DC power supply; connector, 4 terminal(s) for analogue inputs; Mini B USB 2.0 connector for a programming terminal
Maximum cable distance between devicesShielded cable:
InsulationBetween input and internal logic at 500 V AC; Between fast input and internal logic at 500 V AC; Non-insulated between inputs; Between output and internal logic at 500 V AC; Non-insulated between analogue input and internal logic; Non-insulated between analogue inputs
MarkingCE
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit
Height90 mm
Depth70 mm
Width160 mm
Net weight0.63 kg
Contractual warranty
Warranty (in months)18
Environment
StandardsIEC 61131-2; UL 508; CAN/CSA C22.2 No. 213; IACS E10; ANSI/ISA 12-12-01
Product certificationsRCM; cULus; LR; ABS; EAC; DNV-GL; CE; UKCA; cULus HazLoc
Environmental characteristicOrdinary and hazardous location
Resistance to electrostatic discharge8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4
Resistance to conducted disturbances10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Immunity to microbreaks10 ms
Ambient air temperature for operation-10…55 °C (horizontal installation); -10…35 °C (vertical installation)
Ambient air temperature for storage-25…70 °C
Relative humidity10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP degree of protectionIP20 with protective cover in place
Operating altitude0...2000 m
Storage altitude0…3000 m
Vibration resistance3.5 mm at 5…8.4 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 1 gn at 8.4…150 Hz on symmetrical rail; 1 gn at 8.4…150 Hz on panel mounting
Shock resistance147 m/s² for 11 ms
Logistical informations
Country of originTW
Main
Range of productModicon M221
Product or component typeLogic controller
[Us] rated supply voltage24 V DC
Discrete input number24, discrete input 4 fast input conforming to IEC 61131-2 Type 1
Analogue input number2 at 0...10 V
Discrete output typeTransistor
Discrete output number16 transistor 4 fast output
Discrete output voltage24 V DC
Discrete output current0.5 A
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height14.3 cm
Package 1 Width21.0 cm
Package 1 Length11.2 cm
Package 1 Weight832.0 g
Unit Type of Package 2S04
Number of Units in Package 212
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight10.624 kg
Modicon M221 PLC controller in compact format with 0.2µs / Boolean instruction for the automation of simple industrial machines. A total of 40 integrated I/Os, of which 24 are digital (20 standard with 5kHz and 4 HSC with 100kHz) inputs, 16 digital outputs. Additionally 2 analog (0V to 10V / 10Bit) inputs. An RS485/RS232 interface with RJ45 socket for Modbus ASCII/RTU Master/Slave, ASCII character string, Modbus Serial IO scanner. The power supply is via 24VDC. The digital outputs are designed as sink transistors (0.5A). Can be expanded with up to two plug-in modules. 640 kB integrated RAM memory and 2 MB flash memory. Integrated control for up to 4 coordinated axes. Position Control (PTO) with trapezoidal or S-profile for 4 axes in pulse direction (P/D) mode or two axes in CW/CCW mode. Equipped with a slot for SD card, a USB mini-B port for programming, a run/stop switch and QR code for direct access to technical documentation. Local and decentralized I/O expansion with Modicon TM3 I/O system. Programming and configuration using free EcoStruxure Machine Expert - Basic software (download from www.se.com). PLC programming according to IEC 61131-3 in the programming languages instruction list (IL), ladder diagram (LD) or sequential function chart (Grafcet list/SFC). Connection via removable screw terminal block. Ambient temperature during operation -15°C to +50°C. Installation on 35mm DIN rail or directly on control panel. Certified according to CE, cULus Listing Mark, RCM, EAC, LR, ABS, DNV-GL.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1770830
qrcode für Schneider Electric TM221C40U PLC 2AE/24DE/16DA SINK screw terminal