Schneider Electric TM221C40T, EAN: 3606480648748

Schneider Electric TM221C40T PLC control 24DI 16DO

Industrial Material > Automation > PLC Systems

Schneider Electric TM221C40T PLC control 24DI 16DO

Lieske Part No. 663394
Mfg Part No TM221C40T
EAN-Code 3606480648748
Manufacturer Schneider Electric
Here only 347,44 EUR
413,45 EUR incl. VAT

Further information for Schneider Electric TM221C40T PLC control 24DI 16DO

Complementary
Discrete I/O number40
Maximum number of I/O expansion module7 (local I/O-Architecture); 14 (remote I/O-Architecture)
Supply voltage limits20.4…28.8 V
Inrush current35 A
Maximum power consumption in W4.1 W at 24 V (without I/O expansion module); 16 W at 24 V (with max number of I/O expansion module)
Power supply output current0.52 A 5 V for expansion bus; 0.3 A 24 V for expansion bus
Discrete input logicSink or source (positive/negative)
Discrete input voltage24 V
Discrete input voltage typeDC
Analogue input resolution10 bits
LSB value10 mV
Conversion time1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted overload on inputs+/- 30 V DC for 5 min (maximum) for analog input; +/- 13 V DC (permanent) for analog input
Voltage state 1 guaranteed>= 15 V for input
Discrete input current7 mA for discrete input; 5 mA for fast input
Input impedance3.4 kOhm for discrete input; 100 kOhm for analog input; 4.9 kOhm for fast input
Response time35 µs turn-off, I2...I5 terminal(s) for input; 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input; 35 µs turn-on, other terminals terminal(s) for input; 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input; 100 µs turn-off, other terminals terminal(s) for input; 5 µs turn-on, turn-off, Q0...Q1 terminal(s) for output; 50 µs turn-on, turn-off, Q2...Q3 terminal(s) for output; 300 µs turn-on, turn-off, other terminals terminal(s) for output
Configurable filtering time0 ms for input; 3 ms for input; 12 ms for input
Discrete output logicPositive logic (source)
Maximum current per output common4 A
Output frequency100 kHz for fast output (PWM/PLS mode) at Q0...Q1; 5 kHz for output at Q2...Q3; 0.1 kHz for output at Q4...Q15
Absolute accuracy error+/- 1 % of full scale for analog input
Maximum leakage current0.1 mA for transistor output
Mechanical durability20000000 cycles for transistor output
Protection typeOverload and short-circuit protection at 1 A
Reset time1 s automatic reset
Memory capacity256 kB for user application and data RAM with 10000 instructions; 256 kB for internal variables RAM
Data backed up256 kB built-in flash memory for backup of application and data
Data storage equipment2 GB SD card (optional)
Battery typeBR2032 or CR2032X lithium non-rechargeable
Backup time1 year at 25 °C (by interruption of power supply)
Execution time for 1 KInstruction0.3 ms for event and periodic task
Execution time per instruction0.2 µs Boolean
Exct time for event task60 µs response time
Maximum size of object areas255 %TM timers; 512 %M memory bits; 255 %C counters; 512 %KW constant words; 8000 %MW memory words
Realtime clockWith
Regulation loopAdjustable PID regulator up to 14 simultaneous loops
Positioning functionsPosition PTO 2 axe(s)pulse/direction mode (100 kHz); Position PTO 1 axe(s)CW/CCW mode (100 kHz)
Function availableFrequency generator; PWM; PLS
Counting input number4 fast input (HSC mode) at 100 kHz 32 bits
counter functionPulse/direction; Single phase; A/B
Integrated connection typeUSB port with mini B USB 2.0 connector; Non isolated serial link serial 1 with RJ45 connector and RS485 interface ; Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
Supply(serial)serial link supply: 5 V
Transmission rate1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for USB
Communication port protocolUSB port: USB - SoMachine-Network; Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Local signalling1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED (green) for SL1; 1 LED (green) for SL2; 1 LED per channel (green) for I/O state
Electrical connectionremovable screw terminal block for inputs; removable screw terminal block for outputs; terminal block, 3 terminal(s) for connecting the 24 V DC power supply; connector, 4 terminal(s) for analogue inputs; Mini B USB 2.0 connector for a programming terminal
Maximum cable distance between devicesShielded cable:
InsulationBetween input and internal logic at 500 V AC; Between fast input and internal logic at 500 V AC; Non-insulated between inputs; Between output and internal logic at 500 V AC; Non-insulated between analogue input and internal logic; Non-insulated between analogue inputs
MarkingCE
Mounting supportTop hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit
Height90 mm
Depth70 mm
Width160 mm
Net weight0.456 kg
Contractual warranty
Warranty (in months)18
Environment
StandardsIEC 61131-2; UL 508; CAN/CSA C22.2 No. 213; IACS E10; ANSI/ISA 12-12-01
Product certificationsDNV-GL; ABS; EAC; cULus; RCM; LR; CE; UKCA; cULus HazLoc
Environmental characteristicOrdinary and hazardous location
Resistance to electrostatic discharge8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4
Resistance to conducted disturbances10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Immunity to microbreaks10 ms
Ambient air temperature for operation-10…55 °C (horizontal installation); -10…35 °C (vertical installation)
Ambient air temperature for storage-25…70 °C
Relative humidity10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP degree of protectionIP20 with protective cover in place
Operating altitude0...2000 m
Storage altitude0…3000 m
Vibration resistance3.5 mm at 5…8.4 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 1 gn at 8.4…150 Hz on symmetrical rail; 1 gn at 8.4…150 Hz on panel mounting
Shock resistance147 m/s² for 11 ms
Logistical informations
Country of originTW
Main
Range of productModicon M221
Product or component typeLogic controller
[Us] rated supply voltage24 V DC
Discrete input number24, discrete input 4 fast input conforming to IEC 61131-2 Type 1
Analogue input number2 at 0...10 V
Discrete output typeTransistor
Discrete output number16 transistor 2 fast output
Discrete output voltage24 V DC
Discrete output current0.5 A
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height11.000 cm
Package 1 Width14.000 cm
Package 1 Length21.000 cm
Package 1 Weight750.000 g
Unit Type of Package 2S04
Number of Units in Package 212
Package 2 Height30.000 cm
Package 2 Width40.000 cm
Package 2 Length60.000 cm
Package 2 Weight10.100 kg
Unit Type of Package 3P12
Number of Units in Package 3144
Package 3 Height105.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight135.000 kg
Modicon M221 PLC controller in compact format with 0.2µs / Boolean instruction for the automation of simple industrial machines. A total of 40 integrated I/Os, of which 24 are digital (20 standard with 5kHz and 4 HSC with 100kHz) inputs, 16 digital outputs. Additionally 2 analog (0V to 10V / 10Bit) inputs. An RS485/RS232 interface with RJ45 socket for Modbus ASCII/RTU Master/Slave, ASCII character string, Modbus Serial IO scanner. The power supply is via 24VDC. The digital outputs are designed as source transistors (0.5A). Can be expanded with up to two plug-in modules. 640 kB integrated RAM memory and 2 MB flash memory. Integrated control for up to 2 coordinated axes. Position Control (PTO) with trapezoidal or S-profile for 2 axes in pulse direction (P/D) mode or one axis in CW/CCW mode. Equipped with a slot for SD card, a USB mini-B port for programming, a run/stop switch and QR code for direct access to technical documentation. Local and decentralized I/O expansion with Modicon TM3 I/O system. Programming and configuration using free EcoStruxure Machine Expert - Basic software (download from www.se.com). PLC programming according to IEC 61131-3 in the programming languages instruction list (IL), ladder diagram (LD) or sequential function chart (Grafcet list/SFC). Connection via removable screw terminal block. Ambient temperature during operation -15°C to +50°C. Mounting on 35mm DIN rail or directly on control panel. Certified to CE, cULus Listing Mark, CSA, RCM, EAC, LR, ABS, DNV-GL, cCSAus Hazardous Zone.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/663394
qrcode für Schneider Electric TM221C40T PLC control 24DI 16DO