| Complementary |
| Discrete I/O number | 24 |
| Maximum number of I/O expansion module | 7 (local I/O-Architecture); 14 (remote I/O-Architecture) |
| Supply voltage limits | 85…264 V |
| Network frequency | 50/60 Hz |
| Inrush current | 40 A |
| Maximum power consumption in VA | 55 VA at 100...240 V with max number of I/O expansion module; 32 VA at 100...240 V without I/O expansion module |
| Power supply output current | 0.52 A 5 V for expansion bus; 0.16 A 24 V for expansion bus |
| Discrete input logic | Sink or source (positive/negative) |
| Discrete input voltage | 24 V |
| Discrete input voltage type | DC |
| Analogue input resolution | 10 bits |
| LSB value | 10 mV |
| Conversion time | 1 ms per channel + 1 controller cycle time for analogue input analog input |
| Permitted overload on inputs | +/- 30 V DC for 5 min (maximum) for analog input; +/- 13 V DC (permanent) for analog input |
| Voltage state 1 guaranteed | >= 15 V for input |
| Discrete input current | 7 mA for discrete input; 5 mA for fast input |
| Input impedance | 3.4 kOhm for discrete input; 100 kOhm for analog input; 4.9 kOhm for fast input |
| Response time | 35 µs turn-off, I2...I5 terminal(s) for input; 10 ms turn-on for output; 10 ms turn-off for output; 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input; 35 µs turn-on, other terminals terminal(s) for input; 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input; 100 µs turn-off, other terminals terminal(s) for input |
| Configurable filtering time | 0 ms for input; 3 ms for input; 12 ms for input |
| Output voltage limits | 125 V DC; 277 V AC |
| Maximum current per output common | 4 A at COM 2; 7 A at COM 0; 7 A at COM 1 |
| Absolute accuracy error | +/- 1 % of full scale for analog input |
| Switching frequency | 20 switching operations/minute with maximum load |
| Mechanical durability | 20000000 cycles for relay output |
| Minimum load | 1 mA at 5 V DC for relay output |
| Protection type | Without protection at 5 A |
| Reset time | 1 s |
| Memory capacity | 256 kB for user application and data RAM with 10000 instructions; 256 kB for internal variables RAM |
| Data backed up | 256 kB built-in flash memory for backup of application and data |
| Data storage equipment | 2 GB SD card (optional) |
| Battery type | BR2032 or CR2032X lithium non-rechargeable |
| Backup time | 1 year at 25 °C (by interruption of power supply) |
| Execution time for 1 KInstruction | 0.3 ms for event and periodic task |
| Execution time per instruction | 0.2 µs Boolean |
| Exct time for event task | 60 µs response time |
| Maximum size of object areas | 255 %C counters; 8000 %MW memory words; 512 %M memory bits; 512 %KW constant words; 255 %TM timers |
| Realtime clock | With |
| Regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
| Counting input number | 4 fast input (HSC mode) at 100 kHz 32 bits |
| counter function | A/B; Single phase; Pulse/direction |
| Integrated connection type | USB port with mini B USB 2.0 connector; Non isolated serial link serial 1 with RJ45 connector and RS485 interface ; Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface |
| Supply | (serial)serial link supply: 5 V |
| Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for USB |
| Communication port protocol | USB port: USB - SoMachine-Network; Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network |
| Local signalling | 1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED (green) for SL1; 1 LED (green) for SL2; 1 LED per channel (green) for I/O state |
| Electrical connection | removable screw terminal block for inputs; removable screw terminal block for outputs; terminal block, 3 terminal(s) for connecting the 24 V DC power supply; connector, 4 terminal(s) for analogue inputs; Mini B USB 2.0 connector for a programming terminal |
| Maximum cable distance between devices | Shielded cable: |
| Marking | CE |
| Sensor power supply | 24 V DC at 250 mA supplied by the controller |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Depth | 70 mm |
| Width | 110 mm |
| Net weight | 0.395 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 61131-2; UL 508; CAN/CSA C22.2 No. 213; IACS E10; ANSI/ISA 12-12-01 |
| Product certifications | LR; ABS; DNV-GL; RCM; cULus; EAC; CE; UKCA; cULus HazLoc |
| Environmental characteristic | Ordinary and hazardous location |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to IEC 61000-4-8 |
| Resistance to fast transients | 2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Immunity to microbreaks | 10 ms |
| Ambient air temperature for operation | -10…55 °C (horizontal installation); -10…35 °C (vertical installation) |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 with protective cover in place |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 1 gn at 8.4…150 Hz on symmetrical rail; 1 gn at 8.4…150 Hz on panel mounting |
| Shock resistance | 98 m/s² for 11 ms |
| Logistical informations |
| Country of origin | TW |
| Main |
| Range of product | Modicon M221 |
| Product or component type | Logic controller |
| [Us] rated supply voltage | 100...240 V AC |
| Discrete input number | 14, discrete input conforming to IEC 61131-2 Type 1 |
| Analogue input number | 2 at 0...10 V |
| Discrete output type | Relay normally open |
| Discrete output number | 10 relay |
| Discrete output voltage | 5...125 V DC; 5...250 V AC |
| Discrete output current | 2 A |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.600 cm |
| Package 1 Width | 13.900 cm |
| Package 1 Length | 15.500 cm |
| Package 1 Weight | 645.000 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 12.900 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 105.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 164.000 kg |
Modicon M221 PLC controller in compact format with 0.2µs / Boolean instruction for the automation of simple industrial machines. A total of 24 integrated I/Os, of which 14 are digital (10 standard with 5kHz and 4 HSC with 100kHz) inputs, 10 digital outputs. Additionally 2 analog (0V to 10V / 10Bit) inputs. An RS485/RS232 interface with RJ45 socket for Modbus ASCII/RTU Master/Slave, ASCII character string, Modbus Serial IO scanner. The power supply is via 100VAC to 240VAC. The digital outputs are designed as relays (2A). Can be expanded with up to one plug-in module. 640 kB integrated RAM memory and 2 MB flash memory. Integrated control for up to 2 coordinated axes. Position Control (PTO) with trapezoidal or S-profile for 2 axes in pulse direction (P/D) mode or one axis in CW/CCW mode. Equipped with a slot for SD card, a USB mini-B port for programming, a run/stop switch and QR code for direct access to technical documentation. Local and decentralized I/O expansion with Modicon TM3 I/O system. Programming and configuration using free EcoStruxure Machine Expert - Basic software (download from www.se.com). PLC programming according to IEC 61131-3 in the programming languages instruction list (IL), ladder diagram (LD) or sequential function chart (Grafcet list/SFC). Connection via removable screw terminal block. Ambient temperature during operation -15°C to +50°C. Mounting on 35mm DIN rail or directly on control panel. Certified to CE, cULus Listing Mark, CSA, RCM, EAC, LR, ABS, DNV-GL, cCSAus Hazardous Zone.