| Complementary |
| Number of port | 1 CAN port - screw terminal block; 1 USB type C; 2 RS485 - screw terminal block (Modbus serial link); 1 display port - TTL connector; 1 communication module port |
| Input/output number | 6 digital input(s); 5 digital output(s); 7 analog input(s); 4 analog output(s) |
| Discrete input logic | Sink or source (positive/negative) |
| Contacts usage | Volt-free contacts |
| Discrete input voltage | 24 V AC/DC |
| Discrete input current | 2.5 mA |
| Input impedance | 20 kOhm |
| Analogue input type | NTC 103AT-2 Beta 3435 temperature probe - 50...100 °C - resolution: 0.1 °C at 10 kOhm; Pt 1000 temperature probe - 50...400 °C - resolution: 0.1 °C at 2 kOhm; voltage 0...10 V - resolution: 0.001 V at > 10 kOhm; voltage 0...5 V - resolution: 0.001 V at 110 kOhm; current 4...20 mA - resolution: 13 bits at 100 Ohm; direct input at > 10 kOhm |
| Sensor power supply | 5 V DC at 50 mA supplied by the controller; 24 V DC at 125 mA supplied by the controller |
| [Us] rated supply voltage | 230 V AC |
| Power consumption in W | 10 W at 24 V AC |
| Realtime clock | Built-in clock, clock drift |
| Display type | LED |
| Memory type | 1 MB flash; 380 kB RAM |
| Overvoltage category | II |
| Local signalling | 1 LED (green) for USB pendrive download status |
| Mounting support | Panel mounting with accessory; DIN rail |
| Width | 72 mm |
| Height | 110 mm |
| Depth | 60 mm |
| Net weight | 0.180 kg |
| Environment |
| Directives | 2014/30/EU - electromagnetic compatibility; 2014/35/EU - low voltage directive |
| Standards | CAN/CSA-E60730-1; CSA E60730-2-9; EN 60068-2-27; EN 60068-2-6 Fc; EN 60730-1; EN 60730-2-9; UL 60730-1; UL 60730-2-9; IEC 61000-4-2; IEC 61000-4-3; IEC 61000-4-4; IEC 61000-4-5; IEC 61000-4-6; IEC 61000-4-11; UL94 (material V0) |
| Product certifications | EAC (pending); CE; cURus; CSA; RCM (pending) |
| Ambient air temperature for operation | -20…65 °C conforming to UL 60730-1; conforming to EN 60730-1; conforming to EN 60730-2-9 |
| Ambient air temperature for storage | -30…70 °C |
| Relative humidity | 5…95 % non-condensing |
| IP degree of protection | IP20 conforming to EN/IEC 60730 |
| Pollution degree | 2 |
| Operating altitude | 0...2000 m |
| Main |
| Range of product | Modicon M171/M172/M173 |
| Product or component type | Programmable controllers |
| Product specific application | HVAC and pumping solution |
| Variant | Programmable |
| Total inputs/outputs | 22 |
| Discrete input number | 6 |
| Discrete output number | 3 for relay outputs SPST with same common; 2 for relay outputs SPST with independent common |
| Discrete output current | 3 A for relay SPST |
| Analogue input number | 6 configurable by pair; 1 configurable |
| Analogue output number | 1 voltage/current, range: 0…10 V or 4…20 mA; 3 voltage, range: 0...10 V or PWM (10Hz...2 kHz) |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.000 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 13.000 cm |
| Package 1 Weight | 265.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.266 kg |
Die SPS Steuerung Modicon M173 in Optimized Ausführung ist Teil der Modicon M171/M172/M173-Reihe, einem Regelungsangebot für HLK/Pumpenanwendungen. Die Steuerung verfügt über 6 digitale Eingänge, 7 analoge Eingänge, 5 digitale Ausgänge (Relais), 4 analoge Ausgänge. Mit integrierten und optionalen Schnittstellen ist die Steuerung flexibel vernetzbar. Integriert sind zwei RS485 Schnittstellen und einen CAN-Erweiterungsbusanschluss. Es handelt sich um eine programmierbare Logiksteuerung komplette Automatisierungslösungen für HLK- und Pumpenanlagen konzipiert und ist mit einem LCD-Display ausgestattet. Die Steuerung ist kompatibel ist mit E/A-Erweiterungsmodulen und Secure Interfaces. Die Spannungsversorgung erfolgt über 100 - 240 VAC. Die Anschlüsse erfolgen mittels abnehmbaren Schraubklemmleisten (im Lieferumfang enthalten). Die Montage erfolgt auf einer 35mm Hutschiene oder Montageplatte mit Befestigungszubehör. Wird mit kostenfreier Software EcoStruxure Machine Expert - HVAC programmiert.