| Additional features |
| Connection number | 1 CAN port - screw terminal block; 1 USB Type C; 2 RS485 - screw terminal block (Modbus serial link); 1 display interface - TTL connector; 1 communication module port |
| Number of inputs/outputs | 6 digital input(s); 5 digital output(s); 7 analog input(s); 4 analog output(s) |
| Digital logic input | Sink or source (positive/negative) |
| Contact usage | Potential-free contact |
| Input voltage of digital inputs | 24 V AC/DC |
| Discrete input current | 2,5 mA |
| Input impedance | 20 kOhm |
| Measurement inputs | NTC 103AT-2 Beta 3435 temperature sensor - 50-100 °C - resolution: 0.1 °C at 10 kOhm; Pt 1000 temperature sensor - 50-400 °C - resolution: 0.1 °C at 2 kOhm; Voltage 0 - 10 V - resolution: 0.001 V at > 10 kOhm; Voltage 0 - 5 V - resolution: 0.001 V at 110 kOhm; Current 4 - 20 mA - resolution: 13 bits at 100 Ohm; Direct input at > 10 kOhm |
| Sensor power supply | 5 V DC at 50 mA provided by controller; 24 V DC at 125 mA provided by controller |
| [UH,nom] Rated operating voltage | 24 V ± 10 % AC; 20 - 38 V DC |
| Power consumption in W | 10 W at 24 V AC |
| Pulse generator | Built-in clock, clock drift |
| Display type | LED |
| Memory type | 1 MB Flash; 380 kB RAM |
| Over voltage category | II |
| Local signalling | 1 LED (green) for USB pendrive download status |
| Mounting bracket | Mounting on mounting plate with accessories; DIN rail |
| Width | 72 mm |
| Height | 110 mm |
| Depth | 60 mm |
| Product weight | 0,191 kg |
| Main features |
| Product series | Modicon M171/M172/M173 |
| Product or component type | Programmable controllers |
| Product-specific application | HLK and pump solution |
| Variant | Programmable |
| Total number of inputs/outputs | 22 |
| Number of discrete inputs | 6 |
| Number of digital outputs | 3 for relay outputs SPST with common reference conductor; 2 for relay outputs SPST with independent reference conductor |
| Digital output current | 3 A for relay SPST |
| Number of analog inputs | 6 pairwise configurable; 1 configurable |
| Analogue output number | 1 Voltage/Current, range: 0…10 V or 4…20 mA; 3 Voltage, range: 0...10 V or PWM (10Hz...2 kHz) |
| Mounting |
| Policies | 2014/30/EU - electromagnetic compatibility; 2014/35/EU - Low Voltage Directive |
| Standards | CAN/CSA-E60730-1; CSA E60730-2-9; EN 60068-2-27; EN 60068-2-6 Fc; EN 60730-1; EN 60730-2-9; UL 60730-1; UL 60730-2-9; IEC 61000-4-2; IEC 61000-4-3; IEC 61000-4-4; IEC 61000-4-5; IEC 61000-4-6; IEC 61000-4-11; UL94 (Material V0) |
| Product certifications | EAC (pending); CE; cURus; CSA; RCM (pending) |
| Operating ambient temperature | -20…65 °C corresponds to UL 60730-1; corresponds to EN 60730-1; corresponds to EN 60730-2-9 |
| Ambient temperature during storage | -30…70 °C |
| Relative humidity | 5…95 % non-condensing |
| Degree of protection (IP) | IP20 corresponds to EN/IEC 60730 |
| Pollution degree | 2 |
| Operating altitude | 0 - 2.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 7,000 cm |
| VPE 1 width | 9,000 cm |
| VPE 1 length | 13,000 cm |
| Packaging weight (Lbs) | 269,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 15 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 4,340 kg |
Die SPS Steuerung Modicon M173 in Optimized Ausführung ist Teil der Modicon M171/M172/M173-Reihe, einem Regelungsangebot für HLK/Pumpenanwendungen. Die Steuerung verfügt über 6 digitale Eingänge, 7 analoge Eingänge, 5 digitale Ausgänge (Relais), 4 analoge Ausgänge. Mit integrierten und optionalen Schnittstellen ist die Steuerung flexibel vernetzbar. Integriert sind zwei RS485 Schnittstellen und einen CAN-Erweiterungsbusanschluss. Die Steuerung verfügt über einen intergrierten Ventiltreiber (EEVD). Es handelt sich um eine programmierbare Logiksteuerung komplette Automatisierungslösungen für HLK- und Pumpenanlagen konzipiert und ist mit einem LCD-Display ausgestattet. Die Steuerung ist kompatibel ist mit E/A-Erweiterungsmodulen und Secure Interfaces. Die Spannungsversorgung erfolgt über 24 VAC / 24 VDC. Die Anschlüsse erfolgen mittels abnehmbaren Schraubklemmleisten (im Lieferumfang enthalten). Die Montage erfolgt auf einer 35mm Hutschiene oder Montageplatte mit Befestigungszubehör. Wird mit kostenfreier Software EcoStruxure Machine Expert - HVAC programmiert.