| Complementary |
| Local display | With |
| Number or control scheme lines | 0…240 with ladder programming; 0…500 with FBD programming |
| Cycle time | 6…90 ms |
| Backup time | 10 years at 25 °C |
| Clock drift | 12 min/year at 0…55 °C; 6 s/month at 25 °C |
| Checks | Program memory on each power up |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 19.2…30 V |
| Maximum supply current | 100 mA (without extension) |
| Power dissipation in W | 6 W without extension |
| Reverse polarity protection | With |
| Discrete input number | 12 conforming to IEC 61131-2 Type 1 |
| Discrete input type | Resistive |
| Discrete input voltage | 24 V DC |
| Discrete input current | 4 mA |
| Counting frequency | 1 kHz for discrete input |
| Voltage state 1 guaranteed | >= 15 V for I1...IA and IH...IR discrete input circuit; >= 15 V for IB...IG used as discrete input circuit |
| Current state 1 guaranteed | >= 1.2 mA (IB...IG used as discrete input circuit); >= 2.2 mA (I1...IA and IH...IR discrete input circuit) |
| Input compatibility | 3-wire proximity sensors PNP for discrete input |
| Analogue input number | 6 |
| Analogue input type | Common mode |
| Analogue input range | 0...24 V; 0...10 V |
| Temperature probe type | NTC 10k at 25 °C; NTC 1000k at 25 °C; KTY81 210/220/221/222/250; Pt 500 |
| Maximum permissible voltage | 30 V for analogue input circuit |
| Analogue input resolution | 8 bits |
| LSB value | 39 mV for analogue input circuit |
| Conversion time | Smart relay cycle time for analogue input circuit |
| Conversion error | +/- 5 % at 25 °C for analogue input circuit; +/- 6.2 % at 55 °C for analogue input circuit |
| Repeat accuracy | +/- 2 % at 55 °C for analogue input circuit |
| Operating distance | 10 m between stations, with screened cable (sensor not isolated) for analogue input circuit |
| Input impedance | 12 kOhm for IB...IG used as analogue input circuit; 12 kOhm for IB...IG used as discrete input circuit; 7.4 kOhm for I1...IA and IH...IR discrete input circuit |
| Number of outputs | 8 relay |
| Output voltage limits | 24...250 V AC (relay output); 5...30 V DC (relay output) |
| Contacts type and composition | NO for relay output |
| Output thermal current | 8 A for all 8 outputs for relay output |
| Electrical durability | AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1; AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1; DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1; DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1 |
| Switching capacity in mA | >= 10 mA at 12 V (relay output) |
| Operating rate in Hz | 0.1 Hz (at Ie) for relay output; 10 Hz (no load) for relay output |
| Mechanical durability | 10000000 cycles for relay output |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 |
| Clock | With |
| Response time | 10 ms (from state 0 to state 1) for relay output; 5 ms (from state 1 to state 0) for relay output |
| Connections - terminals | Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) semi-solid; Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) solid; Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end |
| Tightening torque | 0.5 N.m |
| Overvoltage category | III conforming to IEC 60664-1 |
| Net weight | 0.38 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 10 ms |
| Product certifications | GOST; UL; CSA; C-Tick; GL |
| Standards | IEC 61000-4-2 level 3; IEC 61000-4-5; IEC 60068-2-27 Ea; IEC 61000-4-12; IEC 61000-4-3; IEC 60068-2-6 Fc; IEC 61000-4-6 level 3; IEC 61000-4-4 level 3; IEC 61000-4-11 |
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529 |
| Environmental characteristic | EMC directive conforming to IEC 61000-6-2; EMC directive conforming to IEC 61000-6-3; EMC directive conforming to IEC 61000-6-4; EMC directive conforming to IEC 61131-2 zone B; Low voltage directive conforming to IEC 61131-2 |
| Disturbance radiated/conducted | Class B conforming to EN 55022-11 group 1 |
| Pollution degree | 2 conforming to IEC 61131-2 |
| Ambient air temperature for operation | -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2; -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 2000 m |
| Maximum altitude transport | 3048 m |
| Relative humidity | 95 % without condensation or dripping water |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | Zelio Logic |
| Product or component type | Compact smart relay |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 10.200 cm |
| Package 1 Length | 13.200 cm |
| Package 1 Weight | 362.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 7.726 kg |
PLC control relay Zelio Logic in a compact design. The small controller (logic module) is designed for simple automation tasks and offers an alternative to classic contactor controls or customer-specific circuit board solutions. With integrated display and buttons that enable programming directly on the device in ladder diagram (LD). A total of 20 integrated I/Os, of which 12 are digital (6 configurable as analog 0 V to 10 V) inputs, 8 digital outputs. The power supply is via 24 VDC. The digital outputs are designed as relays. With integrated clock. Terminal block protection class IP20, front panel protection class IP51. Mounting on 35 mm top hat rail. Programming using free Zelio Soft software in ladder diagram (LD), function block diagram or GRAFCET sequential function chart. Download from www.se.com. Certified according to CE, cULus Listed, CSA, GL, GOST, C-Tick.