| Complementary |
| Local display | With |
| Number or control scheme lines | 0…240 with ladder programming; 0…500 with FBD programming |
| Cycle time | 6…90 ms |
| Backup time | 10 years at 25 °C |
| Clock drift | 12 min/year at 0…55 °C; 6 s/month at 25 °C |
| Checks | Program memory on each power up |
| [Us] rated supply voltage | 100...240 V AC |
| Supply voltage limits | 85…264 V |
| Supply frequency | 50/60 Hz |
| Maximum supply current | 30 mA at 240 V (without extension); 80 mA at 100 V (without extension) |
| Power consumption in VA | 7 VA without extension |
| Isolation voltage | 1780 V |
| Protection type | Against inversion of terminals (control instructions not executed) |
| Discrete input number | 8 |
| Discrete input voltage | 100...240 V AC |
| Discrete input current | 0.6 mA |
| Discrete input frequency | 47...53 Hz; 57...63 Hz |
| Voltage state 1 guaranteed | >= 79 V for discrete input |
| Current state 1 guaranteed | >= 0.17 mA (discrete input) |
| Analogue input number | 0 |
| Input impedance | 350 kOhm for discrete input |
| Number of outputs | 4 relay |
| Output voltage limits | 5...30 V DC (relay output); 24...250 V AC |
| Contacts type and composition | NO for relay output |
| Output thermal current | 8 A for all 4 outputs for relay output |
| Electrical durability | AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1; AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1; DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1; DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1 |
| Switching capacity in mA | >= 10 mA at 12 V (relay output) |
| Operating rate in Hz | 0.1 Hz (at Ie) for relay output; 10 Hz (no load) for relay output |
| Mechanical durability | 10000000 cycles for relay output |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 |
| Clock | With |
| Response time | 50 ms with ladder programming (from state 0 to state 1) for discrete input; 50 ms with ladder programming (from state 1 to state 0) for discrete input; 50...255 ms with FBD programming (from state 0 to state 1) for discrete input; 50...255 ms with FBD programming (from state 1 to state 0) for discrete input; 10 ms (from state 0 to state 1) for relay output; 5 ms (from state 1 to state 0) for relay output |
| Connections - terminals | Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) semi-solid; Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) solid; Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end |
| Tightening torque | 0.5 N.m |
| Overvoltage category | III conforming to IEC 60664-1 |
| Net weight | 0.25 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 10 ms |
| Product certifications | GL; GOST; UL; CSA; C-Tick |
| Standards | IEC 61000-4-4 level 3; IEC 60068-2-27 Ea; IEC 61000-4-5; IEC 61000-4-11; IEC 61000-4-12; IEC 61000-4-3; IEC 60068-2-6 Fc; IEC 61000-4-2 level 3; IEC 61000-4-6 level 3 |
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529 |
| Environmental characteristic | EMC directive conforming to IEC 61000-6-2; EMC directive conforming to IEC 61000-6-3; EMC directive conforming to IEC 61000-6-4; EMC directive conforming to IEC 61131-2 zone B; Low voltage directive conforming to IEC 61131-2 |
| Disturbance radiated/conducted | Class B conforming to EN 55022-11 group 1 |
| Pollution degree | 2 conforming to IEC 61131-2 |
| Ambient air temperature for operation | -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2; -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 2000 m |
| Maximum altitude transport | 3048 m |
| Relative humidity | 95 % without condensation or dripping water |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | Zelio Logic |
| Product or component type | Compact smart relay |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.800 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 10.000 cm |
| Package 1 Weight | 246.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.885 kg |
PLC control relay Zelio Logic in a compact design. The small controller (logic module) is designed for simple automation tasks and offers an alternative to classic contactor controls or customer-specific circuit board solutions. With integrated display and buttons that enable programming directly on the device in ladder diagram (LD). A total of 12 integrated I/Os, of which 8 are digital inputs and 4 are digital outputs. The power supply is via 100 VAC to 240 VAC. The digital outputs are designed as relays. With integrated clock. Terminal block protection class IP20, front panel protection class IP47. Mounting on 35 mm top hat rail. Programming using free Zelio Soft software in ladder diagram (LD), function block diagram or GRAFCET sequential function chart. Download from www.se.com. Certified according to CE, cULus Listed, CSA, GL, GOST, C-Tick.